No.
(Addr.
Name
Hex)
U5-33
Day of the Week
(3003)
Analog Output selection text is: "PID Output 2".
u
U9: Power Monitors
No.
(Addr.
Name
Hex)
U9-01
(0820) Electric Power (GWh)
U9-02
(0821) Electric Power (MWh)
U9-03
Electric Power (kWh)
(0822)
U9-04
Regenerative Power
(0823)
(GWh)
U9-05
Regenerative Power
(0824)
(MWh)
U9-06
Regenerative Power
(0825)
(kWh)
U9-07 to
U9-10
Electric Power Rates 1 to
(0826 to
4
0829)
U9-11 to
U9-14
Regenerative Power
(082A to
Rates 1 to 4
082D)
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Date Week
Displays the current day of the week.
0: Sun
0: Sunday
1: Mon
1: Monday
2: Tues
2: Tuesday
3: Wed
3: Wednesday
4: Thur
4: Thursday
5: Fri
5: Friday
6: Sat
6: Saturday
LCD Display
Shows the total amount of electric power.
GWh Consumed
MWh Consumed
kWh Consumed
Shows the total amount of regenerated power.
GWh Produced
MWh Produced
kWh Produced
These parameters show the electric power rate in Power Unit
Price (o4-19) that is calculated from the total electrical power
consumptions in U9-01 to U9-03.
U9-10: Digit 1 to digit 3
U9-09: Digit 4 to digit 6
U9-08: Digit 7 to digit 9
U9-07: Digit 10 to digit 12
Consumed o ($)
The unit price is set in o4-19, and U9-07 to U9-10 are U9-01 to
U9-03 x o4-19.
These parameters show the regenerative power rate in Power
Unit Price (o4-19) that is calculated from the total electrical
power consumptions in U9-04 to U9-06.
U9-14: Digit 1 to digit 3
U9-13: Digit 4 to digit 6
U9-12: Digit 7 to digit 9
U9-11: Digit 10 to digit 12
Produced o ($)
The unit price is set in o4-19, and U9-11 to U9-14 are U9-04 to
U9-06 x o4-19.
Description
Description
000 000 000 kWh
U9-03
U9-02
U9-01
000 000 000 kWh
U9-06
U9-05
U9-04
000 000 000 000
U9-10
U9-09
U9-08
U9-07
000 000 000 000
U9-14
U9-13
U9-12
U9-11
B.14 U: Monitors
Analog
Unit
Output Level
No signal output
1
available
Analog
Unit
Output Level
No signal output
1 GWh
available
No signal output
1 MWh
available
No signal output
1 kWh
available
No signal output
1 GWh
available
No signal output
1 MWh
available
No signal output
1 kWh
available
No signal output
available
B
No signal output
available
319