YASKAWA Z1000U Technical Manual page 309

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
S2-18
Sequence Timer 4 Day
(3217)
Selection
S2-19
Sequence Timer 4
(3218)
Selection
S2-20
Sequence Timer 4
(3219)
Reference Source
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Tmr 4 Day Sel
Sets the days for which sequence timer 4 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Tmr 4 Seq Sel
Sets the action that occurs when sequence timer 4 is active.
0: Digital Out Only
0: Digital output only
1: Run
1: Run
2: Run - PID Disable
2: Run - PID disable
Selects the frequency reference source used for running the drive
Tmr 4 Ref Source
when sequence timer 4 is active (only applicable when S2-19 is
0: Operator (d1-01)
set to 1 or 2).
1: Operator (d1-02)
0: Operator (d1-01)
2: Operator (d1-03)
1: Operator (d1-02)
3: Operator (d1-04)
2: Operator (d1-03)
4: Terminals
3: Operator (d1-04)
5: Serial Com
4: Terminals
5: Serial communication
Description
B.12 S: HVAC Function
Values
Page
Default: 0
169
Range: 0 to 10
Default: 0
169
Range: 0 to 2
Default: 0
170
Range: 0 to 5
309