YASKAWA Z1000U Technical Manual page 291

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

u
E2: Motor 1 Parameters
No.
(Addr.
Name
Hex)
E2-01
Motor Rated Current
(030E)
E2-03
Motor No-Load Current No-Load Current
(0310)
E2-04
Number of Motor Poles Number of Poles
(0311)
E2-05
Motor Line-to-Line
(0312)
Resistance
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units based on drive model:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Sets the motor nameplate full load current in amps.
Automatically set during Auto-Tuning.
Motor Rated FLA
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
Sets the number of motor poles. Automatically set during
Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set
Term Resistance
during Auto-Tuning.
B.6 E: Motor Parameters
Description
Values
Page
<1>
Default:
Min.: 10% of
drive rated
current
131
Max.: 150% of
drive rated
<2>
current
<1>
Default:
Min.: 0.00 A
131
<2>
Max.: E2-01
Default: 4
Min.: 2
Max.: 48
<1>
Default:
Min.: 0.000 Ω
Max.: 65.000 Ω
B
291