YASKAWA Z1000U Technical Manual page 355

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

u
Wiring Diagram for Multiple Connections
Figure D.3
explains the wiring diagrams for multiple connections using MEMOBUS/Modbus communication.
n
RS-485 Interface
Note:
Turn on DIP switch S1 on the bypass controller located at the end of the network. If S1 is missing, then an external 120 ohm resistor must
be placed across terminals TXRX+ and TXRX-. All other slave devices must have this DIP switch set to the OFF position (or if S1 is
missing, no external resistor is used).
u
Network Termination
The two ends of the MEMOBUS/Modbus network line have to be terminated with a 120 ohm resistor between the TXRX+
and TXRX- signals. The bypass has a built in termination resistor that can be enabled or disabled using DIP switch S1. If a
bypass is located at the end of a network line, enable the termination resistor by setting DIP switch S1 to the ON position.
Disable the termination resistor on all slaves that are not located at the network line end.
Note:
Some bypass controllers do not have DIP switch S1. If this is the case, then an external 120 ohm resistor must be placed across the
TXRX+ and TXRX- signals if the bypass controller is at the end of a network line.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
COMMON
+
CONTROLLER
(customer-supplied)
-
SHLD
Figure D.3 Connection Diagram for Multiple Connections
D.3 Connecting to a Network
Bypass Drive
TB3
Bypass
1
IG5
Control
Board A2
2
TXRX+
S1
3
TXRX-
4
SHLD
OFF
Bypass Drive
TB3
Bypass
1
IG5
Control
Board A2
2
TXRX+
S1
3
TXRX-
4
SHLD
OFF
Bypass Drive
TB3
Bypass
1
IG5
Control
Board A2
2
TXRX+
S1
3
TXRX-
ON
4
SHLD
D
355