YASKAWA Z1000U Technical Manual page 334

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

C.3 Connecting to a Network
C.3 Connecting to a Network
This section explains how to connect the bypass to a BACnet network and the network termination required for a connection.
u
Network Cable Connection
Follow the instructions below to connect the bypass to a BACnet network.
1.
With the power shut off, connect the communications cable to the bypass and the master. Use terminal TB3 for
BACnet.
Note:
Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for
the communications cables, and properly shielded clamps to prevent problems caused by electrical interference.
2.
Check or set the termination resistor selection at all slaves. Use the description in
335
for slaves that are Z1000U Bypasses.
3.
Switch the power on.
4.
Set the parameters needed for serial communications (Z3-01 through Z3-09) using the digital operator.
5.
Shut the power off and wait until the display on the digital operator goes out completely.
6.
Turn the power back on.
7.
The bypass is now ready to begin communicating with the master.
334
Figure C.2 Serial Communications Cable Connection Terminal (TB3)
TB3
SHLD
4
3
TXRX-
2
TXRX+
1
IG5
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Shield
Transmit/Receive (-)
Transmit/Receive (+)
Isolated Ground Reference