B.6 E: Motor Parameters
B.6 E: Motor Parameters
u
E1: V/f Pattern for Motor 1
No.
(Addr.
Name
Hex)
E1-03
V/f Pattern Selection
(0302)
E1-04
Maximum Output
(0303)
Frequency
E1-05
Maximum Voltage
(0304)
E1-06
Base Frequency
(0305)
E1-07
Middle Output
(0306)
Frequency
E1-08
Middle Output
(0307)
Frequency Voltage
E1-09
Minimum Output
(0308)
Frequency
E1-10
Minimum Output
(0309)
Frequency Voltage
E1-11
Middle Output
(030A)
Frequency 2
<1> Value is specific to 200 V class drives; double the value for 400 V class models.
<2> Parameter setting is not reset to the default value when drive is initialized.
<3> Default setting is dependent on parameter o2-04, Drive Model Selection.
<4> Default is 230 or 460, depending on parameter o2-04, Drive Model Selection setting.
<5> Default is 17.3 or 34.6, depending on parameter o2-04, Drive Model Selection setting.
<6> Default is 10.2 or 20.4, depending on parameter o2-04, Drive Model Selection setting.
290
LCD Display
V/F Selection
0: 50 Hz, Constant torque 1
0: 50 Hz
1: 60 Hz, Constant torque 2
1: 60 Hz Saturation
2: 50 Hz, Constant torque 3 (50 Hz base)
2: 50 Hz Saturation
3: 72 Hz, Constant torque 4 (60 Hz base)
3: 72 Hz
4: 50 Hz, Variable torque 1
4: 50 Hz VT1
5: 50 Hz, Variable torque 2
5: 50 Hz VT2
6: 60 Hz, Variable torque 3
6: 60 Hz VT1
7: 60 Hz, Variable torque 4
7: 60 Hz VT2
8: 50 Hz, High starting torque 1
8: 50 Hz HST1
9: 50 Hz, High starting torque 2
9: 50 Hz HST2
A: 60 Hz, High starting torque 3
A: 60 Hz HST1
B: 60 Hz, High starting torque 4
B: 60 Hz HST2
C: 90 Hz (60 Hz base)
C: 90 Hz
D: 120 Hz (60 Hz base)
D: 120 Hz
E: 180 Hz (60 Hz base)
E: 180 Hz
F: Custom V/f E1-04 through E1-13 settings define the V/f
F: Custom V/F
pattern
Max Frequency
These parameters are only applicable when E1-03 is set to F.
Max Voltage
To set linear V/f characteristics, set the same values for E1-07
and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure
that the four frequencies are set according to these rules:
Base Frequency
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
Mid Frequency A
Mid Voltage A
Min Frequency
Min Voltage
Mid Frequency B
Description
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Values
Page
<2>
Default: F
127
Range: 0 to 9;
A to F
<3>
Default:
Min.: 40.0 Hz
Max.: 400.0 Hz
<4>
Default:
Min.: 0.0 V
130
Max.: 255.0 V
<1>
<3>
Default:
Min.: 0.0 Hz
Max.: E1-04
<3>
Default:
Min.: 0.0 Hz
Max.: E1-04
<5>
Default:
Min.: 0.0 V
Max.: 255.0 V
<1>
<3>
Default:
Min.: 0.0 Hz
Max.: E1-04
<6>
Default:
Min.: 0.0 V
Max.: 255.0 V
<1>
Default: 0.0 Hz
Min.: 0.0
Max.: E1-04

Advertisement

Table of Contents
loading

Table of Contents