YASKAWA Z1000U Technical Manual page 386

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

E.1 APOGEE FLN Set-Up
E.1 APOGEE FLN Set-Up
A Yaskawa America representative is responsible for proper configuration of the bypass for its primary application, while a
Siemens Building Technologies representative is responsible for field panel programming to make use of the bypass
functionality in the building automation system. As such, there must be coordination between the Yaskawa America and
Siemens Building Technologies representatives to ensure that the programming of the drive is consistent with the particular
application requirements. After verifying that the drive installation and wiring are correct, apply power to the drive.
Drive Communication Parameter Settings on page 386
communication and control.
u
Bypass Parameter Settings for APOGEE FLN Communications
Parameter Number
Z1-07
Z1-08
Z3-02
Z3-03
Z3-01
NOTICE: A Yaskawa representative should set the drive parameters to their appropriate values. Changes made to the parameters other
than what is listed in the table above can result in damaging the drive or building equipment.
386
lists parameters and values required for proper APOGEE FLN
Table E.1 Drive Communication Parameter Settings
Digital Operator Display
Reference Source
Run Source
Serial Comm Adr
Serial Baud Rate
Protocol Select
Settings for APOGEE FLN Communication
2: Serial Com
2: Serial Com
Select the bypass address
2: 4800 Baud
2: P1
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual