YASKAWA Z1000U Technical Manual page 119

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.
b5-38
b5-39
Setting 0: No Decimal Places
Setting 1: One Decimal Place
Setting 2: Two Decimal Places
Setting 3: Three Decimal Places
n
b5-40: Frequency Reference Monitor Content During PID
Sets the content of the frequency reference monitor display (U1-01) when PID control is active.
No.
b5-40
Frequency Reference Monitor Content During PID
Setting 0: Frequency Reference after PID
Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference
Monitor U1-01 displays the frequency reference value.
n
b5-46: PID Setpoint Monitor Unit Selection
Sets the HOA keypad display units in U5-01 and U5-04 when b5-20 is set to 3.
No.
b5-46
Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
n
b5-47: PID Output Reverse Selection 2
Determines whether a negative PID output reverses the direction of drive operation. When the PID function is used to trim
the frequency reference (b5-01 = 3), this parameter has no effect and the PID output will not be limited
(same as b5-11 = 1).
No.
b5-47
Setting 0: Reverse Disabled
Negative PID output will be limited to 0 and the drive output will be stopped.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Name
PID Setpoint User Display
PID Setpoint Display Digits
Name
Name
PID Setpoint Monitor Unit Selection
Name
PID Output Reverse Selection 2
5.2 b: Application
Setting Range
Determined by
1 to 60000
Determined by
0 to 3
Setting Range
0, 1
Setting Range
0 to 14
Setting Range
0, 1
Default
b5-20
b5-20
Default
0
Default
0
5
Default
1
119