5.14 Z: Bypass Parameters
Run Delay with Preset Speed Examples
DAMPER ACTUATOR OUTPUT
VFD FREQUENCY REFERENCE
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
VFD FREQUENCY REFERENCE
VFD OUTPUT FREQUENCY
FAULT: FB02 BAS Ilock Open
Figure 5.56 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
180
VFD RUN COMMAND
BAS INTERLOCK INPUT
Figure 5.55 Run Delay with Preset Speed Example: Default Setting
VFD RUN COMMAND
t1
t2
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Z1-15 Interlck Wait Tm
1 t
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 10.0 sec
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
t3
2 t
t3