YASKAWA Z1000U Technical Manual page 298

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

B.8 H Parameters: Multi-Function Terminals
H3-oo
Function
Setting
DC Injection Braking
6
current
Overtorque/undertorque
7
detection level
Stall Prevention level
8
during run
Output frequency lower
9
limit level
B
PID feedback
C
PID setpoint
D
Frequency bias
Motor temperature (PTC
E
input)
F
Through mode
Differential PID
16
feedback
1F
HAND Reference
25
Secondary PI Setpoint
26
Secondary PI Feedback PI2 Feedback
u
H4: Analog Outputs
No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal FM
(041D)
Monitor Selection
H4-02
Multi-Function Analog
(041E)
Output Terminal FM
Gain
H4-03
Multi-Function Analog
(041F)
Output Terminal FM
Bias
Multi-Function Analog
H4-04
Output Terminal AM
(0420)
Monitor Selection
H4-05
Multi-Function Analog
(0421)
Output Terminal AM
Gain
H4-06
Multi-Function Analog
(0422)
Output Terminal AM
Bias
Multi-Function Analog
H4-07
Output Terminal FM
(0423)
Signal Level Selection
Multi-Function Analog
H4-08
Output Terminal AM
(0424)
Signal Level Selection
298
H3 Multi-Function Analog Input Settings
LCD Display
10 V = Drive rated current
DC Brake Current
10 V = Drive rated current
Torque Det Level
10 V = Drive rated current
Stall Prev Level
10 V = E1-04 (maximum output frequency)
Ref Lower Limit
PID Feedback1
10 V = 100%
PID Set Point
10 V = 100%
Freq Ref Bias 2
10 V = E1-04 (maximum output frequency)
10 V = 100%
Motor PTC
Not Used
Set this value when using the terminal in the pass-through mode.
10 V = 100%
PID Feedback 2
Sets the frequency reference when in HAND Mode and parameter Z1-41, HAND
Hand Ref
Speed Reference Selection, is set to 1 (Analog).
PI2 Setpoint
10 V = S3-02 (maximum output frequency)
10 V = S3-02 (maximum output frequency)
LCD Display
Selects the data to be output through multi-function analog
output terminal FM.
Term FM FuncSel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Terminal FM Bias
Selects the data to be output through multi-function analog
output terminal AM.
Terminal AM Sel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal AM that is equal to 100% of
the selected monitor value.
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Terminal AM Bias
Term FM Lvl Sel
0: 0 to 10 V
0-10 VDC
1: -10 to +10 V
1: -10 +10 VDC
2: 4 to 20 mA
2: 4-20 mA
Term AM Lvl Sel
0: 0 to 10 V
0-10 VDC
1: -10 to +10 V
1: -10 +10 VDC
2: 4 to 20 mA
2: 4-20 mA
Description
Description
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Page
147
147
147
147
147
148
148
148
148
148
148
148
148
Values
Page
Default: 102
Range: 000 to
148
621
Default: 100.0%
Min.: -999.9
148
Max.: 999.9
Default: 0.0%
Min.: -999.9
148
Max.: 999.9
Default: 103
Range: 000 to
148
621
Default: 50.0%
Min.: -999.9
148
Max.: 999.9
Default: 0.0%
Min.: -999.9
148
Max.: 999.9
Default: 0
149
Range: 0 to 2
Default: 0
149
Range: 0 to 2