E.3 Slope and Intercept Conversion
Several drive parameters are available for monitoring purposes. These include FREQ OUTPUT (Point 3), SPEED (Point 5),
CURRENT (Point 6), TORQUE (Point 7), POWER (Point 8), DRIVE TEMP (Point 9), KWH (Point 10), and RUN TIME
(Point 12). These points can be unbundled for monitoring or used in various global control strategies.
u
Drive Controlled Feedback
The most typical application is Supervisory Control. The sensor for the control variable (e.g., water temperature) is hard-wired
to the drive and the control device (fan) is modulated using the PID control loop that is built into the drive. The setpoint for
the control variable (water temperature setpoint) is unbundled and commanded by the field panel, based on some building
control strategy implemented in PPCL.
When this strategy is used, the point to unbundle and command for the setpoint is INPUT REF 1 (Point 60). The control
variable (e.g., water temperature) can be monitored by unbundling PID FEEDBACK (Point 62). These points are provided in
units of percent, where 0% and 100% correspond to the range of the sensor being used to measure the control variable. These
points have default units in Hz. If other units are required, unbundle these points with appropriate slopes and intercepts. The
new intercept will be equal to the lowest value of the desired range. You can define a new slope and intercept using the formula
below to convert the units:
Conversion Example
You are controlling water temperature from a cooling tower using the drive to control a fan. The temperature sensor has a
range of 30 °F to 250 °F. To unbundle the setpoint (INPUT REF 1), for commanding in degrees Fahrenheit, where 0 to 60 Hz
is equal to 30 °F to 250 °F:
New Intercept = 30 (the temperature that corresponds to 0%)
Formula Notes:
Desired Range = Range Maximum – Range Minimum
Range of Existing Point = Existing Range Maximum – Existing Range Minimum
u
Field Panel Controlled Feedback
In this strategy, the sensor is connected to the APOGEE FLN network at a remote location, and the control loop is executed
in PPCL. The drive speed command is passed from the field panel to the drive by commanding INPUT REF 1 (Point 60).
NOTICE: This strategy is not recommended because the loop is being closed over the network. Delays from processor scan time and
network traffic can cause degradation or loss of control. Damage to HVAC equipment may result.
Unbundle the FEEDBACK
To unbundle the feedback (PID FEEDBACK) for monitoring in degrees Fahrenheit:
New Intercept = 30
Formula Notes:
Desired Range = Range Maximum – Range Minimum
Range of Existing Point = Existing Range Maximum – Existing Range Minimum
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
(Desired Range) x (Slope of Existing Point)
New Slope =
(Range of Existing Point)
(60 - 0)Hz x (0.01)
New Slope =
(100 - 0)%
(Desired Range) x (Slope of Existing Point)
New Slope =
(Range of Existing Point)
(250 - 30)°F x (0.1)
New Slope =
(100 - 0)%
(Desired Range) x (Slope of Existing Point)
New Slope =
(Range of Existing Point)
(250 - 30)°F x (0.1)
New Slope =
(100 - 0)%
E.3 Slope and Intercept Conversion
= 0.006
= 0.022
2
= 0.022
2
E
389