Application Selection - YASKAWA Z1000U Technical Manual

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

4.5

Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to values
appropriate for the application that was selected.
An Application Preset can either be selected from the Application Selection display in the Setup Group
Setting Parameters on page
Note:
An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to initialize
the drive by setting Z1-01 to 1 or 3 prior to selecting an Application Preset.
WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change the
I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
No.
Name
A1-06
Application Preset
(0127)
u
Setting 1: Fan Application
No.
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
L5-01
Number of Auto Restart Attempts
L6-01
Torque Detection Selection 1
u
Setting 2: Fan with PID Control Application
No.
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
b5-01
PID Function Setting
b5-03
Integral Time Setting (I)
b5-08
PID Primary Delay Time Constant
b5-13
PID Feedback Low Detection Level
b5-14
PID Feedback Low Detection Time
C1-01
Acceleration Time 1
L5-01
Number of Auto Restart Attempts
L6-01
Stall Prevention Selection during Deceleration
u
Setting 3: Return Fan with PID Control Application
No.
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
b5-01
PID Function Setting
b5-03
Integral Time Setting (I)
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
88) or in parameter A1-06. The following presets can be selected:
Table 4.6 Application Selection
LCD Display
Application Sel
0: Standard
0: General
1: Fan
1: Fan General
2: Fan with PID Control
2: Fan PID
3: Return Fan with PID Control
3: Fan ReturnAir/PID
4: Cooling Tower Fan
4: Cooling Tower
5: Cooling Tower Fan with PID Control
5: CoolingTower/PID
6: Pump (Secondary)
6: Pump Secondary
7: Pump with PID Control
7: Pump PID
Table 4.7 Fan: Parameter Settings
Name
Table 4.8 Fan with PID Control: Parameter Settings
Parameter Name
Table 4.9 Return Fan with PID Control: Parameter Settings
Parameter Name
Description
Default Setting
1: Coast to Stop
1: Reverse operation disabled
60 s
10
5: UL3 at speed agree (Alarm)
Default Setting
1: Coast to Stop
1: Reverse operation disabled
1: Output frequency = PID output 1
30 s
2 s
2%
25 s
60 s
10
5: UL3 at speed agree (Alarm)
Default Setting
1: Coast to Stop
1: Reverse operation disabled
1: Output frequency = PID output 1
30 s
4.5 Application Selection
(Refer to Quick
Values
Default: 0
Range: 0 to 7
4
91