H2: Multi-Function Digital Outputs
No.
(Addr.
Name
Hex)
Terminal M1-M2
H2-01
function selection
(040B)
(relay)
Terminal M3-M4
H2-02
function selection
(040C)
(relay)
Terminal MD-ME-MF
H2-03
function selection
(040D)
(relay)
H2-oo
Function
Setting
0
During run
1
Zero speed
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
Power supply error
8
During baseblock (N.O.) BaseBlk 1
Torque detection 1
B
(N.O.)
C
Frequency reference loss Loss of Ref
E
Fault
Not Used (Through
F
mode)
10
Minor fault
Fault reset command
11
active
13
Speed agree 2
14
User-set speed agree 2
15
Frequency detection 3
16
Frequency detection 4
Torque detection 1
17
(N.C.)
1A
During Reverse
1B
During baseblock (N.C.) BaseBlk 2
1E
Restart enabled
Drive overheat pre-
20
alarm (oH)
2F
Maintenance period
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Refer to H2 Multi-Function Digital Output Settings on pages
M1-M2 Func Sel
295
to
296
M3/M4 Func Sel
MD/ME/MF FuncSel
H2 Multi-Function Digital Output Settings
LCD Display
During RUN 1
Closed: A Run command is active or voltage is output.
Open: Output frequency is above the minimum output frequency set in E1-09.
Zero Speed
Closed: Output frequency is below the minimum output frequency set in E1-09.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
Fref/Fout Agree1
set to L4-02).
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
Fref/Set Agree 1
hysteresis set to L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
Freq Detect 1
determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01 with
Freq Detect 2
hysteresis determined by L4-02.
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
Power Supply Err
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
Closed: An overtorque or undertorque situation has been detected.
Trq Det 1 N.O.
Closed: Analog frequency reference has been lost.
Fault
Closed: Fault occurred.
Set this value when using the terminal in the pass-through mode.
Not Used
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
Minor Fault
expected life span.
Closed: A command has been entered to clear a fault via the input terminals or
Reset Cmd Active
from the serial network.
Fref/Fout Agree2
Closed: When drive output frequency equals the frequency reference ±L4-04.
Fref/Set Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
Closed: When the drive output frequency is less than or equal to the value in L4-03
Freq Detect 3
±L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03
Freq Detect 4
±L4-04.
Open: Overtorque or undertorque has been detected.
Trq Det 1 N.C.
Reverse Dir
Closed: Drive is running in the reverse direction.
Open: Drive has entered the baseblock state (no output voltage).
Dur Flt Restart
Closed: An automatic restart is performed
Closed: Heatsink temperature exceeds the parameter L8-02 value, or an external
OH Prealarm
device has triggered an oH2 alarm via multi-function input H1-oo = B.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
Maintenance
may require maintenance.
B.8 H Parameters: Multi-Function Terminals
Description
for descriptions of setting values.
Description
Values
Page
Default: 0
135
Range: 0 to 164
Default: 1
135
Range: 0 to 164
Default: 2
135
Range: 0 to 164
Page
136
136
136
137
137
138
138
138
138
139
139
139
139
139
139
139
139
140
140
B
139
139
141
141
141
141
295

Advertisement

Table of Contents
loading

Table of Contents