6.7 Auto-Tuning Fault Detection

6.7
Auto-Tuning Fault Detection
Auto-Tuning faults in this section are displayed on the digital operator and will cause the motor to coast to a stop. Auto-Tuning
faults do not trigger a multi-function digital output set for fault or alarm output.
An Endo error on the digital operator display indicates Auto-Tuning has successfully completed with discrepancies in the
calculations. Restart Auto-Tuning after fixing the cause of the Endo error.
The drive may be used in the application if no cause can be identified despite the existence of an Endo error.
An Ero error indicates that Auto-Tuning has not completed successfully. Check for the cause of the error using the tables in
this section, and perform Auto-Tuning again after fixing the cause.
u
Auto-Tuning Codes, Causes, and Possible Solutions
HOA Keypad Display
End3
Cause
The correct current rating printed on the motor
nameplate was not entered into T1-04
HOA Keypad Display
End4
Cause
The calculated slip is outside the allowable range Make sure the data entered for Auto-Tuning is correct.
HOA Keypad Display
End5
Cause
The calculated resistance value is outside the
allowable range
HOA Keypad Display
End7
Cause
The entered no-load current value was outside the
allowable range
Auto-Tuning results were less than 5% of the
motor rated current
HOA Keypad Display
Er-01
Cause
Motor data or data entered during Auto-Tuning
was incorrect
Motor output power and motor-rated current
settings (T1-02 and T1-04) do not match
Motor rated current and detected no-load current
are inconsistent
Base frequency and motor rated speed (T1-05 and
T1-07) do not match
232
Table 6.11 Auto-Tuning Codes, Causes, and Possible Solutions
Rated Current Setting Alarm (displayed after Auto-Tuning is complete)
• Check the setting of parameter T1-04.
• Check the motor data and repeat Auto-Tuning.
Adjusted Slip Calculation Error
Resistance Tuning Error
• Double-check the data entered for the Auto-Tuning process.
• Check the motor and motor cable connection for faults.
No-Load Current Alarm
Check and correct faulty motor wiring.
Double-check the data entered for the Auto-Tuning process.
Motor Data Error
• Make sure motor data entered to T1-oo match motor nameplate information.
• Restart Auto-Tuning and enter the correct information.
• Check the drive and motor capacities.
• Correct the settings of parameters T1-02 and T1-04.
• Check the motor rated current and no-load current.
• Correct the settings of parameters T1-04 and E2-03.
• Correct the settings of parameters T1-05 and T1-07.
• Check that the correct number of poles were entered to T1-06.
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions