Advertisement

Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0.
page
143.
Setting 1: 0 to 10 V without Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted.
page
143.
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
page 146
for a list of functions and descriptions.
No.
H3-10
<1> Default is 0 when b5-01 is set to 0.
Default is B when b5-01 is set to 1 or 3.
n
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way
as parameters H3-03 and H3-04 for analog input A1.
No.
H3-11
H3-12
n
H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter prevents erratic drive control when using a "noisy" analog reference. Drive operation becomes more
stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog signals.
No.
H3-13
n
H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for "Analog input enable" (H1-oo = C), the value set to H3-14
determines which analog input terminals are enabled when the input is closed. All of the analog input terminals will be enabled
all of the time when H1-oo≠ C. The terminals not set as the target are not influenced by input signals.
No.
H3-14
Setting 1: A1 Only Enabled
Setting 2: A2 Only Enabled
Setting 3: A1 and A2 Only Enabled
Setting 4: A3 Only Enabled
Setting 5: A1 and A3 Only Enabled
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Name
Terminal A2 Function Selection
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Name
Analog Input Filter Time Constant
Name
Analog Input Terminal Enable Selection
Refer to Setting 0: 0 to 10 V with Zero Limit on
Refer to Setting 1: 0 to 10 V without Zero Limit on
Refer to Multi-Function Analog Input Terminal Settings on
Setting Range
0 to 26
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0.00 to 2.00 s
Setting Range
5.7 H: Terminal Functions
Default
<1>
Default
100.0%
0.0%
Default
0.03 s
Default
1 to 7
7
5
145