YASKAWA Z1000U Technical Manual page 134

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

5.7 H: Terminal Functions
Status
Up (10)
Down (11)
Open
Closed
Open
Closed
Note:
1. An oPE03 alarm occurs when only one of the Up/Down functions is programmed to a digital input.
2. An oPE03 alarm occurs when the Up/Down function is assigned to the terminals and a different digital input is programmed for the
Accel/decel ramp hold function. Refer to the Troubleshooting chapter in the User Manual packaged with the drive for more information
on alarms.
3. The Up/Down function can only be used for External reference 1. Consider this when using Up/Down and the external reference switching
command (H1-oo = 2).
Using the Up/Down Function with Frequency Reference Hold (d4-01)
• If the frequency reference hold function is disabled (d4-01 = 0), the Up/Down frequency reference will be reset to 0 when
the Run command is cleared or the power is cycled.
• When d4-01 = 1, the drive will save the frequency reference set by the Up/Down function. When the Run command or the
power is cycled, the drive will restart with the saved reference value. Close the Up or Down input without an active Run
command to reset the saved value.
Using the Up/Down Function with Frequency Reference Limits
The value for the lower frequency reference limit depends on the parameter d4-10 setting. This value can be set by an analog
input or parameter d2-02. When a Run command is applied, the lower limits function as follows:
• If the lower limit is set by d2-02 only, the drive accelerates to this limit as soon as a Run command is entered.
• If the lower limit is determined by an analog input only, the drive accelerates to the limit when both the Run command and
an Up or Down command are active. The drive will not start running if only the Run command is active.
• If the lower limit is set by both an analog input and d2-02, and the analog limit is higher than the d2-02 value, the drive
accelerates to the d2-02 value when a Run command is input. When the d2-02 value is reached, the drive accelerates to the
analog limit only if an Up or Down command is set.
Figure 5.18
shows an Up/Down function example with a lower frequency reference limit set by d2-02, and the frequency
reference hold function both enabled and disabled.
Setting 14: Fault Reset
When the drive detects a fault condition, the fault output contact closes, the drive output shuts off, and the motor coasts to
stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). After removing the Run
command, clear the fault either by pressing the RESET key on the HOA keypad or closing a digital input configured as a Fault
Reset (H1-oo = 14).
Note:
Remove the Run command prior to resetting a fault. Fault Reset commands are ignored while the Run command is present.
134
Open
Open
Closed
Closed
Output frequency
upper limit
Accelerates to
lower limit
Lower limit
FWD run/stop
ON
Up command
Down command
Power supply
Figure 5.18 Up/Down Command Operation
Drive Operation
Hold current frequency reference
Increase frequency reference
Decrease frequency reference
Hold current frequency reference
d4-01 = 1
Same
frequency
ON
Hold
ON
frequency
reset
ON
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
d4-01 = 0
ON

Advertisement

Table of Contents
loading

Table of Contents