YASKAWA Z1000U Technical Manual page 177

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

Setting 4: HAND-BYPASS
When drive powers up , the bypass will get a "HAND" command and needs an "OFF" command to stop.
n
Z1-07: Speed Reference Select
Selects the frequency reference source 1.
Note:
If a Run command is input to the drive, but the frequency reference entered is 0 or below the minimum frequency, the AUTO or HAND
indicator LED on the HOA keypad will light and the OFF indicator will flash.
No.
Z1-07
Setting 0: HOA Keypad
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references from d1-01 to d1-04.
• entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in
used.
Table 5.27 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal
Signal Level
0 to 10 Vdc
A1
-10 to +10 Vdc
0 to 10 Vdc
A2
-10 to +10 Vdc
0 to 10 Vdc
A3
-10 to +10 Vdc
0 to 10 V
2 k
Figure 5.53 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to
current input.
Table 5.28 Analog Input Settings for Frequency Reference Using a Current Signal
Signal
Terminal
Level
4 to 20 mA
A2
0 to 20 mA
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Name
Speed Reference Select
Signal Level
Function Selection
Selection
H3-01 = 0
(Frequency Reference Bias)
H3-01 = 1
H3-09 = 0
(Frequency Reference Bias)
H3-09 = 1
H3-05 = 0
(Frequency Reference Bias)
H3-05 = 1
Drive
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
Parameter Settings
Signal Level
Function
Selection
Selection
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-09 = 3
Parameter Settings
Gain
H3-02 = 0
H3-03
H3-10 = 0
H3-11
H3-06 = 0
H3-07
+10 V
4 k
Customer
+/- 10 V
Supply
OR
-10 V
Common
Table 5.28
Gain
H3-11
5.14 Z: Bypass Parameters
Setting Range
0 to 3
Table 5.27
Bias
H3-04
Set jumper S1 on the terminal
H3-12
board to "V" for voltage input.
Set DIP switch S4 on the
H3-08
terminal board to "AI".
Drive
+V 10.5 V, 20 mA power supply
-10 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
for an example to set terminal A2 for
Bias
Make sure to set jumper S1 on the
H3-12
terminal board to "I" for current
input.
Default
1
for the input
Notes
5
Notes
177