YASKAWA Z1000U Technical Manual page 88

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

4.3 The Drive and Programming Modes
u
Simplified Setup Using the Quick Setting Group
The Quick Setting Group lists only the basic parameters necessary to set up the bypass. This group expedites the startup process
by showing only the most important bypass parameters.
n
Quick Setting Parameters
Table 4.5
lists the parameters in the Quick Setting Group.
Use the Programming Mode to access parameters not displayed in the Quick Setting Group.
No.
Name
A1-06
Application Preset
(0127)
E1-05
Maximum Voltage
(0304)
E2-01
Motor Rated Current
(030E)
Z1-07
(85CC) Speed Reference Select
Z1-08
(85CD) Run Command Select
Z1-09
(85CE) HAND Mode Drive
Speed Reference
Z1-37
(85EA) Set Time
Z3-01
Serial Communications
(8500)
Protocol Select
Z3-02
Serial Communications
(8501)
Node Address Select
88
Table 4.5 Quick Setting Group Parameters
LCD Display
Application Sel
0: Standard
0: General
1: Fan
1: Fan General
2: Fan with PID Control
2: Fan PID
3: Return Fan with PID Control
3: Fan ReturnAir/PID
4: Cooling Tower Fan
4: Cooling Tower
5: Cooling Tower Fan with PID Control
5: CoolingTower/PID
6: Pump (Secondary)
6: Pump Secondary
7: Pump with PID Control
7: Pump PID
Max Voltage
These parameters are only applicable when E1-03 is set to F.
Sets the motor nameplate full load current in amps.
Motor Rated FLA
Automatically set during Auto-Tuning.
Determines the source of the Frequency Reference sent from
Spd Ref Sel
the Bypass Controller to the Drive.
0: Operator
0: Operator
1: Analog Input
1: Analog Input
2: Bypass Serial
2: Bypass Serial
3: Option Board
3: Option Board (CN5)
Determines the source of the Auto Mode Run command used
Run Cmd Sel
by the Bypass Controller.
0: Operator
0: Operator
1: Bypass DI
1: Bypass Controller Digital Input
2: Bypass Serial
2: Bypass Serial
3: Option Board
3: Option Board (CN5)
This is the speed reference used when the Drive is running in
Hand Fref
HAND mode. Units are in Hz.
Changes the LCD display to time setting to set the Real Time
Set Time
Clock.
0: Normal display
0: Normal display
1: Time Setting
1: Displays time and date setting mode
2: Reset Time
2: Reset time
Serial Protocol
Selects the bypass serial communications protocol.
0: Modbus
0: Modbus
1: N2
1: N2
2: P1
2: P1
3: BACnet
3: BACnet
Node Address
Selects the bypass serial communications node address.
Description
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Values
Page
Default: 0
100
Range: 0 to 7
<2>
Default:
Min.: 0.0 V
130
Max.: 255.0 V
<1>
<2>
Default:
Min.: 10% of
drive rated
current
131
Max.: 150% of
drive rated
<3>
current
Default: 1
177
Range: 0 to 3
Default: 1
178
Range: 0 to 3
Default: 10.0
<4>
Hz
178
Min.: 0.0
Max.: 60.0
Default: 0
183
Range: 0 to 2
Default: 3
191
Range: 0 to 3
Default: 1
Min.: 0
191
Max.: 127