6.9 Troubleshooting without Fault Display

6.9
Troubleshooting without Fault Display
This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor.
Performance Fine-Tuning on page 200
• Motor hunting and oscillation
• Poor motor torque
• Poor speed precision
• Poor motor torque and speed response
• Motor noise
u
Common Problems
Cannot Change Parameter Settings
Motor Does Not Rotate Properly after Pressing RUN Button or after
Entering External Run Command
Motor is Too Hot
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Motor Stalls During Acceleration or With Large Loads
Drive Frequency Reference Differs from the Controller Frequency Reference Command
Excessive Motor Oscillation and Erratic Rotation
Noise From Drive or Motor Cables When the Drive is Powered On
Ground Fault Circuit Interrupter (GFCI) Trips During Run
Connected Machinery Vibrates When Motor Rotates
PID Output Fault
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)
Output Frequency is not as High as Frequency Reference
Buzzing Sound from Motor at 2 kHz
Motor Does Not Restart after Power Loss
The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals (Terminals DM+ and DM-)
u
Cannot Change Parameter Settings
Cause
The drive is running the motor
(i.e., the Run command is present).
The operator is not in the Parameter Setup Mode
(the screen will display "PAr").
A multi-function contact input terminal is set to allow
or restrict parameter editing
(H1-01 through H1-07 = 1B).
The wrong password was entered.
Undervoltage was detected.
236
for guidance on troubleshooting.
Common Problems
Motor Does Not Rotate
Motor Rotates in the Opposite Direction from the Run Command
Motor Rotates in One Direction Only
Unexpected Noise from Connected Machinery
Oscillation or Hunting
• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.
• See what mode the operator is currently set for.
• Parameters cannot be edited when in the Setup Mode ("STUP"). Switch modes so that "PAr"
appears on the screen.
• When the terminal is open, parameters cannot be edited.
• Turn on the multi-function contact input set to 1B.
• If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
• Reset the password.
If you cannot remember the password:
Scroll to Z1-02. Press
• Set a new password to parameter Z1-03.
• Check the drive input power voltage by looking at the DC bus voltage (U1-07).
• Check all main circuit wiring.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Possible Solutions
Refer to The Drive and Programming Modes on page
OFF
and
simultaneously. Parameter Z1-03 will appear.
Refer to Motor
Page
236
237
239
239
239
240
240
240
241
241
241
241
242
242
242
242
243
243
243
86.