YASKAWA Z1000U Technical Manual page 93

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

u
Setting 6: Pump (Secondary) Application
No.
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
d2-03
Master Speed Reference Lower Limit
L5-01
Number of Auto Restart Attempts
L6-01
Stall Prevention Selection during Deceleration
u
Setting 7: Pump with PID Control Application
No.
b1-04
Reverse Operation Selection
b5-01
PID Function Setting
b5-03
Integral Time Setting (I)
b5-08
PID Primary Delay Time Constant
b5-13
PID Feedback Low Detection Level
b5-14
PID Feedback Low Detection Time
b5-15
PID Sleep Function Start Level
b5-16
PID Sleep Delay Time
C1-01
Acceleration Time 1
d2-03
Master Speed Reference Lower Limit
L5-01
Number of Auto Restart Attempts
L6-01
Stall Prevention Selection during Deceleration
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Table 4.12 Pump (Secondary): Parameter Settings
Parameter Name
Table 4.13 Pump with PID Control: Parameter Settings
Parameter Name
4.5 Application Selection
Default Setting
1: Reverse operation disabled
20 s
20%
10
5: UL3 at speed agree (Alarm)
Default Setting
1: Reverse operation disabled
1: Enabled (PID output becomes output frequency reference)
15 s
10.0 s
2%
25 s
72%
25.5 s
20 s
20%
10
5: UL3 at speed agree (Alarm)
4
93