B.14 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
u
UB: Bypass Control Monitors
No.
Name
(Addr. Hex)
UB-01
Motor Current
(8780)
UB-02
Bypass Digital Input States
(8781
UB-03
Bypass Digital Output States
(8782)
UB-04
Bypass Digital Output States
(8783)
UB-05
Bypass Controller Status
(8784)
Register 1
UB-06
Bypass Controller Status
(8785)
Register 2
UB-07
Bypass Controller Active Faults
(8786)
Register 1
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Format is XXX.X amps.
View status of bypass digital inputs XXXXXXXX
Where X = 0 (not asserted) or 1 (asserted) The right-most digit is the status of digital input
1.
View status of bypass digital outputs
XXXXXXXX
Where X = 0 (not asserted) or 1 (asserted) The right-most digit is the status of digital output
1.
View status of bypass digital outputs
XXXXXXXX
Where X = 0 (not asserted) or 1 (asserted) The right-most digit is the status of digital output
9.
UB-05 =
00 000 000
UB-06 =
00 000 000
Note:
When read over serial communications, address 8785H, contains two
additional bits of information:
Bit 8: "0" when Z1-07 = 2, otherwise "1".
Bit 9: "0" when Z1-08 = 2, otherwise "1".
UB-07 =
00 000 000
Description
0
HAND Mode
0
OFF Mode
0
AUTO Mode
0
DRIVE Mode
0
BYPASS Mode
0
Smoke Purge Bypass Active
0
Smoke Purge Drive Active
0
Safety Open
0
BAS Interlock Open
0
RUN Active
0
Fault Active
0
Auto Transfer Active
0
Remote Transfer Active
0
Energy Savings Active
0
Motor 1 Selected
0
Motor 2 Selected
0
Drive Fault
0
Safety Open
0
BAS Interlock Open Time Out
0
External Fault Bypass (EFB)
0
Reserved
0
Motor Overload
0
External Motor 1 Overload
0
External Motor 2 Overload
B.14 U: Monitors
Unit
Amp
B
311