Advertisement

6.9 Troubleshooting without Fault Display
n
Motor Does Not Rotate
Cause
The drive is not in the Drive Mode.
The HAND button was pressed.
Auto-Tuning has just completed.
A Fast Stop was executed and has
not yet been reset.
Settings are incorrect for the source
that provides the Run command.
There is faulty wiring in the control
circuit terminals.
The drive has been set to accept the
frequency reference from the
incorrect source.
The terminal set to accept the main
speed reference is set to the incorrect
voltage and/or current.
Selection for the sink/source mode
and the internal/external power
supply is incorrect.
Frequency reference is too low.
Multi-function analog input is set up
to accept gain for the frequency
reference, but no voltage (current)
has been provided.
The OFF button was pressed when
the drive was started from a
REMOTE source.
Motor starting torque is too low.
Frequency reference value is too low
or the drive does not accept the value
entered.
The sequence Start/Stop sequence is
set up incorrectly.
238
• Check if the DRV light on the HOA keypad is lit.
• Enter the Drive Mode to begin operating the motor.
Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the
source, the HAND button LED must be on. If the source is REMOTE, it must be off.
Press the HAND button to solve the problem.
• When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will
not be accepted unless the drive is in the Drive Mode.
• Use the HOA keypad to enter the Drive Mode.
Reset the Fast Stop command.
Check parameter b1-02 (Run Command Selection).
Set b1-02 so that it corresponds with the correct Run command source.
0: HOA keypad
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
• Check the wiring for the control terminal.
• Correct wiring mistakes.
• Check the input terminal status monitor (U1-10).
Check parameter b1-01 (Frequency Reference Selection 1).
Set b1-01 to the correct source of the frequency reference.
0: HOA keypad
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If
terminal A2 is used, check parameter H3-09. If terminal A3 is used, check parameter H3-06.
A1, A2, and A3 Input Signal Selection on page
Check wire jumper connection between terminals SC and SP.
• Check the frequency reference monitor (U1-01).
• Increase the frequency by changing the maximum output frequency (E1-09).
• Check the multi-function analog input settings.
• Check if analog input A1, A2, or A3 is set for frequency reference gain (H3-02, H3-10, H3-06 = 1). If so, check
if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is
applied to the gain input.
• Check if H3-02, H3-10, and H3-06 have been set to the proper values.
• Check if the analog input value has been set properly. (U1-13 to U1-15)
• Pressing the OFF button will decelerate the drive to stop.
• Switch off the Run command and then re-enter a new Run command.
• Set o2-02 to 0 to disable the OFF button.
Refer to Motor Performance Fine-Tuning on page
Enter a value that is above the minimum output frequency determined by E1-09.
• If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-08 are not
set to 0.
• If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03 through H1-08 must
be set to 0. Terminal S1 will become the Start, terminal S2 will become the Stop input.
Possible Solutions
Refer to The Drive and Programming Modes on page
Refer to The Drive and Programming Modes on page
73.
200.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
86.
86.
Refer to Terminals