YASKAWA Z1000U Technical Manual page 283

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

No.
(Addr
Name
Hex.)
b3-19
Number of Speed
(01F2)
Search Restarts
b3-24
Speed Search Method
(01C0)
Selection
b3-25
(01C8) Speed Search Wait Time SpdSrch WaitTime
b3-27
Start Speed Search
(01C9)
Select
Speed Search Operation
b3-31
Current Level 1 (Current
(0BC0)
Detection 1)
Speed Search Operation
b3-32
Current Level 2 (Current
(0BC1)
Detection 2)
Speed Search Selection
b3-33
when Run Command is
(0B3F)
Given during Uv
Backspin Search
b3-50
Direction Judgment
(0BC7)
Time 1
Backspin Search
b3-51
Direction Judgment
(0BC8)
Time 2
b3-52
Backspin Search
(0BC9)
Deceleration Time 1
b3-53
Backspin Search
(0BCA)
Deceleration Time 2
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
u
b5: PID Control
No.
(Addr.
Name
Hex)
b5-01
PID Function Setting
(01A5)
b5-02
(01A6) Proportional Gain
Setting (P)
b5-03
(01A7) Integral Time Setting (I) PID I Time
b5-04
(01A8) Integral Limit Setting
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
LCD Display
Sets the number of times the drive can attempt to restart when
Num of SrchRestr
performing Speed Search.
SpdSrch Method
1: Speed Estimation
1: Speed Estimation
2: Current Detection
2: CurrentDetect2
Sets the time the drive must wait between each Speed Search
restart attempt.
Selects a condition to activate Speed Search Selection at Start
SpdSrch Start AI
(b3-01) or External Speed Search Command 1 or 2 from the
0: Start from 0
multi-function input.
1: start SPD
0: Triggered when a Run command is issued (normal).
1: Triggered when an external baseblock is released.
Set the current level to use to limit the output current during a
Search (I2) Lvl1
Speed Search.
Set the current level at which to end the Speed Search for
Search (I2) Lvl2
Current Detection Type Speed Search 2.
Activates and deactivates Speed Search at start in accordance
with whether a Run command was issued during an
SpdSrch Start UV
undervoltage (Uv) condition. Function is active when a
0: Disabled
momentary power loss (L2-01 = 1 or 2), Speed Search at start
1: Enabled
(b3-01 = 1), and coasting to a stop (b1-03 = 1) are enabled.
0: Disabled
1: Enabled
Bkspin Srch Time1
Adjusts the direction of Speed Search to allow for backspin.
Bkspin Srch Time2
Sets the search frequency deceleration rate when searching from
BkspinSrchDecel1
the direction command when the momentary power loss time is
shorter than the time set in b3-50.
Sets the search frequency deceleration rate for a Speed Search
from the opposite direction of the direction command when the
BkspinSrchDecel2
momentary power loss time is equal to or longer than the time
set in b3-51.
LCD Display
PID Mode
0: Disabled
0: Disabled
1: Enabled (PID output becomes output frequency reference)
1: Enabled D=Fdbk
3: Enabled (PID output added to frequency reference)
3: Fref+PID D=Fdbk
Sets the proportional gain of the PID controller.
PID Gain
Sets the integral time for the PID controller.
Sets the maximum output possible from the integrator as a
percentage of the maximum output frequency.
PID I Limit
Description
Description
B.3 b: Application
Values
Page
Default: 3
Min.: 0
107
Max.: 10
Default: 2
107
Range: 1, 2
Default: 0.5 s
Min.: 0.0
107
Max.: 30.0
Default: 0
107
Range: 0, 1
Default: 1.50
Min.: 1.50
108
Max.: 3.50
Default: 1.20
Min.: 0.00
108
Max.: 1.49
Default: 0
108
Range: 0, 1
Default: 0.0 s
Min.: 0.0
108
Max.: 10.0
Default: 0.0 s
Min.: 0.0
108
Max.: 10.0
Default: 2.0 s
Min.: 0.0
110
Max.: 10.0
Default: 2.0 s
Min.: 0.0
110
Max.: 10.0
Values
Page
Default: 0
114
B
Range: 0, 1, 3
Default: 2.00
Min.: 0.00
114
Max.: 25.00
Default: 0.5 s
Min.: 0.0
114
Max.: 360.0
Default: 100.0%
Min.: 0.0
114
Max.: 100.0
283