Page 1
Low Harmonic Drive for HVAC Applications Z1000U HVAC MATRIX Drive Quick Start Guide Type: CIMR-ZU Models: 200 V Class: 7.5 to 75 kW (10 to 100 HP ND) 400 V Class: 5.5 to 260 kW (7.5 to 350 HP ND) To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance.
Page 2
Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • When ordering a new copy of the manual due to damage or loss, contact Yaskawa or a Yaskawa representative and provide the manual number shown on the front cover.
Page 5
Failure to comply could result in death or serious injury. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 6
Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 7
When wiring over long distances, be sure to take preventative measures such as using thick cables or series wiring to lower the impedance of wiring. Contact Yaskawa or a Yaskawa representative for details.
Page 8
Grounding the Power Supply Yaskawa recommends using a dedicated ground for the power supply, as the drive is designed to run with a 1:1 ratio relative to the power supply. Ground other devices as directed in the specifications for those devices. Take particular care when connecting sensitive electronic devices.
Selecting a Circuit Breaker or Circuit Interrupter Yaskawa recommends installing a Ground Fault Circuit Interrupter (GFCI) to the power supply side. The GFCI should be designed for use with AC drives (e.g., Type B according to IEC/EN 60755).
Figure i.1 shows the allowable load characteristics for a Yaskawa standard motor. Use a motor designed specifically for operation with a drive when 100% continuous torque is needed at low speeds. 25% ED (or 15 min)
Page 11
• In Open Loop Vector Control for PM motors, the allowable load inertia is approximately 50 times higher than the motor inertia. Contact Yaskawa or a Yaskawa representative for questions concerning applications with larger inertia. • When using a holding brake in Open Loop Vector Control for PM motors, release the brake prior to starting the motor.
Page 12
Hot Surfaces Wait 5 minutes or longer ● until the unit has cooled. Figure i.2 Warning Information Example and Position YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Figure i.3 Drive Nameplate Information Example <1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
NOTICE: Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling. Single Drive Installation Figure i.6 shows the installation distance required to maintain sufficient space for airflow and wiring. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 16
A – No space between drive and C – Space between drive and washer washer D – Spring washer open B – Spring washer fully closed Figure i.7 Spring Washer YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 17
3. Lower the drive when ready to install in the enclosure panel. Stop lowering when near the floor, then slowly begin lowering the drive again until the drive is placed correctly. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 18
Refer to the Z1000U HVAC MATRIX Drive User Manual TOEP C710636 10 for IP20/UL Type 1 and IP00/Open Chassis dimensions. The Z1000U HVAC MATRIX Drive User Manual is posted on the Yaskawa website, www.yaskawa.com. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
NOTICE: Do not connect more than one multi-function input to one terminal. Improper wiring may result in drive malfunction. Use an external power supply when sharing a terminal with more than one input. Do not use the built-in +24 V power supply. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 20
Supply Switch (maximum 150 mA) - Factory-Installed Jumper twisted-pair shielded line control circuit terminal main circuit terminal shielded line Figure i.12 Drive Standard Connection Diagram (Example: Model 2o0028) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 21
<8> Use jumper S5 to select between voltage or current output signals at terminals AM and FM. Set parameters H4-07 and H4-08 accordingly. <9> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for use as a feedback-type signal. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 22
Main Circuit Protective Cover Close the protective cover after wiring the main circuit terminals on drive models 2o0028 to 2o0081 and 4o0011 to 4o0077. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 23
Refer to UL Standards Compliance on page 82 for information on UL compliance. The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge selections. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 24
(8 to 1) (78.1 to 95.5) 2.5 to 4 2.5 to 4 1.2 to 2.0 p1, n1 (14) (14 to 12) (14) (14 to 12) (10.4 to 17.4) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
(14 to 5) (34.7 to 43.4) 2.5 to 4 2.5 to 4 1 to 1.4 p1, n1 (14) (14 to 12) (14) (14 to 12) (8.9 to 12.4) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 26
(5 to 3) (78.1 to 95.5) 2.5 to 4 2.5 to 4 1 to 1.4 p1, n1 (14) (14 to 12) (14) (14 to 12) (8.9 to 12.4) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 27
(1 to 300) (278 to 347) 2.5 to 4 2.5 to 4 1.2 to 2.0 p1, n1 (14) (14 to 12) (14) (14 to 12) (10.4 to 17.4) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 28
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in abnormal operation of drive or equipment. Refer to Figure i.16 when using multiple drives. Do not loop the ground wire. Figure i.16 Multiple Drive Wiring YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 29
(Frequency reference bias) • Voltage or current input must be selected by jumper S1 and H3-05. Frequency reference common E (G) Ground for shielded lines and option cards – YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 30
<1> Enable the termination resistor in the last drive in an APOGEE FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 network by setting DIP switch S2 to the ON position. Refer to TOEPC71063610 Z1000U User Manual section on Control I/O Connections for more information. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 31
– – (4.4 to 8.9) (20 to 14) Ferrule-Type Wire Terminals Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends with insulated sleeves. See Table i.11 for dimensions. Figure i.18 Ferrule Dimensions YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 32
Strip length 5.5 mm. D – Blade depth of 0.4 mm or less Blade width of 2.5 mm or less Figure i.19 Terminal Board Wiring Guide YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 33
External 24 Vdc Power Supply (Terminals SN and SP) Sinking Mode (NPN) 24 Vdc 24 Vdc External 24 Vdc ±10% Sourcing Mode (PNP) 24 Vdc 24 Vdc External 24 Vdc ±10% YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 34
H4-07 Terminal FM signal level selection 0: 0 to 10 Vdc 1: -10 to 10 Vdc 0 to 2 H4-08 Terminal AM signal level selection 2: 4 to 20 mA YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 35
(Drives are shipped with the SW screw installed at the OFF position.) Table i.18 Asymmetrical Grounded Network Characteristics Diagram Grounded at the corner of the delta Grounded at the middle of the side Single-phase, grounded at the end point YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 36
MA MB MC A – SW (ON) B – Screw (OFF) Figure i.24 EMC Filter Switch Location (Drive Models 2E0028, 2W0028, 4E0011 to 4E0034, and 4W0011 to 4W0034) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 37
(Drive Models 2E0042, 2W0042, 2E0054, 2W0054, 4E0040 to 4E0077, and 4W0040 to 4W0077) A – SW (ON) B – Screw (OFF) Figure i.26 EMC Filter Switch Location (Drive Models 2E0104, 2W0104, 2E0130, 2W0130, 4E0096, 4W0096, 4E0124, and 4W0124) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 38
(Drive Models 2E0154, 2W0154, 2E0192, 2W0192, 4E0156, 4W0156, 4E0180, and 4W0180) A – SW (ON) B – Screw (OFF) Figure i.28 EMC Filter Switch Location (Drive Models 2E0248, 2W0248, 4EU0216, 4W0216, 4E0240, and 4W0240) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 39
24 V Control Power Supply Unit Location A –Power Supply Terminal Block TB1 Figure i.30 24 V Control Power Supply Unit Location (Models 2P0028, 2W0028, 4P0011 to 4P0034, and 4W0011 to 4W0034) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 40
(Models 2P0104, 2W0104, 2P0130, 2W0130, 4P0096, 4W0096, 4P0124, and 4W0124) A –Power Supply Terminal Block TB1 Figure i.33 24 V Control Power Supply Unit Location (Models 2P0154, 2W0154, 2P0192, 2W0192, 4P0156, 4W0156, 4P0180, and 4W0180) YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 41
Tightening screws beyond the specified tightening torque may cause erroneous operation, damage the terminal block, or cause a fire. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 42
0.25 to 1.5 (24 to 16 AWG) Ferrule-Type Wire Terminals Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends with insulated sleeves. See Table i.11 for dimensions. Figure i.38 Ferrule Dimensions Table i.21 Ferrule Terminal Types and Sizes...
Page 43
• If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly. Properly ground the drive. Tighten control circuit and grounding terminal screws. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 44
Analog signal line wiring should not exceed 50 m. – Disconnect the internal EMC filter by moving the SW screw to the OFF position for floating, impedance grounded, or asymmetrically grounded networks. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Lit while the drive is in HAND mode. Refer to AUTO LED and HAND LED Indications on page HAND Light for details. HAND ALM LED Light Lit when the drive detects an alarm or error. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 46
(F1) HOME Pressing returns to the top menu (Frequency Reference). Pressing returns to the previous display. Indicates forward motor operation. FWD/REV Indicates reverse motor operation. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 47
AUTO mode, Ready, No run command input. HAND Short blink (15% duty) AUTO HAND AUTO mode, stopped by a Fast- Stop from a Multi-Function Digital Input. Double blink YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 48
<5> The Frequency Reference appears after the initial display that shows the product name. <6> The information that appears on the display will vary depending on the drive. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 49
Check control circuit terminal connections. Drive control terminal status Open all control circuit terminals (off). Status of the load and connected Decouple the motor from the load. machinery YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
H3-05 = 0 H3-06 = 0 Set DIP switch S4 on the H3-07 H3-08 (Frequency Reference Bias) terminal board to “AI”. -10 to +10 Vdc H3-05 = 1 YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 52
If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 operation error will be displayed on the digital operator and the drive will not run. b1-02: Run Command Selection for AUTO Mode Determines the Run command selection for AUTO mode. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 53
The stopping time is determined by the inertia and the friction in the driven system. command Output frequency Drive output is shut off Motor speed Figure i.45 Coast to Stop YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 54
Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t after t has expired to start the drive. Run command Output Drive output shut off frequency Run wait time t Figure i.48 Coast with Timer YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 55
C1-04 Figure i.50 shows an operation example for changing accel/decel. times. The example below requires that the stopping method be set for “Ramp to stop” (b1-03 = 0). YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 56
Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for “Auxiliary frequency 1”, then d1-02 becomes the reference for Multi-Step Speed 2. Select the different speed references as shown in Table i.30. Figure i.51 illustrates the multi-step speed selection. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 57
0.0 to 110.0% 0.0% Internal frequency reference d2-01 Frequency Reference Upper Limit Operating range Frequency Reference Lower Limit d2-02 Set frequency reference Figure i.52 Frequency Reference: Upper and Lower Limits YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 58
Use this setting if no motor overheat protection is desired or if multiple motors are connected to a single drive. If multiple motors are connected to a single drive, install a thermal relay for each motor as shown in Figure i.53. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 59
E1-06, Motor Base Speed, with L1-02 set to one minute. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 60
The PTC must exhibit the characteristics shown in Figure i.56 in one motor phase. The motor overload protection of the drive expects 3 of these PTCs to be connected in a series. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 61
This section explains how to operate the drive with the motor decoupled from the load during a test run. Before Starting the Motor Check the following items before operation: • Ensure the area around the motor is safe. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 62
Select the best V/f pattern according to the application and motor characteristics. Perform Rotational Auto-Tuning for V/f Control if using Energy Saving functions. Open Loop Vector Control for PM (A1-02 = 5) Perform Auto-Tuning as described. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Refer to the Z1000U HVAC MATRIX Drive User Manual TOEP C710636 10 for information on Troubleshooting and complete product instructions necessary for proper installation, set-up, troubleshooting and maintenance. The Z1000U HVAC MATRIX Drive User Manual is posted on the Yaskawa website, www.yaskawa.com. Fault Detection Fault Displays A fault is indicated by a code on the data display and the ALM LED is on.
Page 64
Option Card Fault at Option Port CN5-B oFb01 Option not properly connected Option Card Fault at Option Port CN5-B oFb02 Same type of option card is currently connected YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 65
Snubber Discharge Resistor Overheat Phase Order Detection Fault The phase rotation direction for the input power supply changed. Internal Resistance Fault An operation failure occurred in the snubber discharge resistor circuit. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 66
CALL Communication has not yet been established. MEMOBUS/Modbus Communication Error Control data was not received for the CE detection time set to H5-09. CrST Cannot Reset Drive Disabled YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 67
• The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the alarm detection level. • Detection requires setting multi-function analog inputs H3-02, H3-10, or H3-06 to E. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 68
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 • E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Carrier Frequency Setting Error oPE11 Correct the setting for the carrier frequency. oPE16 Energy Savings Constants Error YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Turn off the main power supply if the above methods do not reset the fault. Reapply power after the HOA keypad display has turned off. When an “SC” error occurs, contact Yaskawa or a Yaskawa agent before cycling the power to the drive. Note: If the Run command is present, the drive will disregard any attempts to reset the fault.
Stall Prevention is available during acceleration, deceleration, and during run. <6> Ground Protection Electronic circuit protection Charge LED of Capacitor for Remains lit until control power supply voltage falls below 50 V Control Power Supply YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 71
<7> An IP20/UL Type 1 enclosure drive requires a UL Type 1 kit. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
3: Coast with timer b3-18 Detection Time (Speed Sets the time to detect Speed Search restart. Reverse Operation 0: Reverse enabled Estimation Type) b1-04 Selection 1: Reverse disabled YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 73
1: Display the frequency reference (U1-01) b5-15 Start Level sleep/snooze function. before PID compensation has been added. PID Sleep Delay Time Sets a delay time before the sleep/snooze b5-16 function is triggered. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 74
Sets the frequency to switch between accel/ Switching Frequency decel time settings C2-01 S-Curve Characteristic S-curve at acceleration start. at Accel Start C2-02 S-Curve Characteristic S-curve at acceleration end. at Accel End YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 75
Sets the signal level at terminal FM that is sent to contact outputs 62 and 162. H4-02 Output Terminal FM equal to 100% of the selected monitor Gain value. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 76
Reference Loss H5-09 CE Detection Time when the frequency reference is lost. Adjustment may be needed when networking several drives. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 77
0: Disabled reduction time. 1: Enabled 0: Disabled High Current Alarm 1: Enabled. L8-41 Selection An alarm is triggered at output currents above 150% of drive rated current. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Verify the following installation conditions to ensure that other devices and machinery used in combination with drive models ZooEoooo and ZooWoooo also comply with EMC guidelines. Place the drive in the enclosure. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 81
Failure to comply may result in death or serious injury. A – Braided shield cable C – Cable clamp (conductive) B – Metal panel Figure i.59 Ground Area YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 82
Conditions of Acceptability Install the drive and peripherals in a suitable enclosure for end use. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 83
Yaskawa-recommended crimp terminals, tools, and insulation caps. Use the appropriate wire gauge and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department. Select suitable crimp terminals in accordance with national, state, or local codes.
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external power supply shall be a UL Listed Class 2 power supply source or equivalent only. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 87
The motor temperature is continually calculated while the drive is powered up. L1-02: Motor Overload Protection Time Setting Range: 0.1 to 5.0 min Factory Default: 1.0 min YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 88
The drive stops the motor using the Fast Stop time set in parameter C1-09. Setting 3: Alarm Only The operation is continued and an oH3 alarm is displayed on the digital operator. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 89
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge selections. The external power supply shall be a CSA certified or cUL Listed Class 2 power source only or equivalent. Refer to Table i.
Page 90
Revision: EMC filter switch for models 2E0248, 2W0248, 4EU0216, 4W0216, 4E0240, and Installation 4W0240 Parameter Table Addition: H2-06 = 0 (0.1 kWh units) July 2014 – – First Edition. This manual supports drive software version PRG: 6112. YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 91
This Page Intentionally Blank YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide...
Page 92
Z1000U HVAC MATRIX Drive Quick Start Guide YASKAWA AMERICA, INC. 2121, Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: +1-800-YASKAWA (927-5292) or +1-847-887-7000 Fax: +1-847-887-7310 http://www.yaskawa.com DRIVE CENTER (INVERTER PLANT) 2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan Phone: +81-930-25-2548 Fax: +81-930-25-3431 http://www.yaskawa.co.jp...