YASKAWA Z1000U Technical Manual page 324

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

B.15 Z: Bypass Parameters
u
Z2: Bypass Control Input/Output
No.
(Addr.
Name
Hex)
Z2-01
(8563) Digital Input 1 Function
Select
Z2-02
(8564) Digital Input 2 Function
Select
Z2-03
(8565) Digital Input 3 Function
Select
Z2-04
(8566) Digital Input 4 Function
Select
Z2-05
(8567) Digital Input 5 Function
Select
Z2-06
(8568) Digital Input 6 Function
Select
Z2-07
Digital Input 7 Function
(8569)
Select
Z2-08
(856A) Digital Input 8 Function
Select
Z2-09
(856B) Digital Input 1 Invert
Select
Z2-10
(856C) Digital Input 2 Invert
Select
Z2-11
(856D) Digital Input 3 Invert
Select
Z2-12
(856E) Digital Input 4 Invert
Select
Z2-13
(856F) Digital Input 5 Invert
Select
Z2-14
(8570) Digital Input 6 Invert
Select
Z2-15
(8571) Digital Input 7 Invert
Select
324
LCD Display
0: Unused (Available for Serial Comms)
3: DRV Multi-Function Input S3 (H1-03 Setting)
DI-1 Func Sel
4: DRV Multi-Function Input S4 (H1-04 Setting)
5: DRV Multi-Function Input S5 (H1-05 Setting)
6: DRV Multi-Function Input S6 (H1-06 Setting)
7: DRV Multi-Function Input S7 (H1-07 Setting)
DI-2 Func Sel
7: DRV Multi-Function Input S8 (H1-08 Setting)
21: Run (AUTO Mode)
22: Run Enable (Safety)
23: Run Interlock (BAS)
DI-3 Func Sel
24: Remote Transfer to Bypass
25: Smoke Purge Bypass Run to Destruction
26: Smoke Purge Drive Run to Destruction at Smoke Purge
Preset Speed. Bypass controller will stay in this state even if the
DI-4 Func Sel
drive faults or is unavailable.
27: Motor OR Select (2-Motor OR function; 0/1 for Motor 1/2.
Behavior defined by Z1-11)
28: Motor AND Select (2-Motor AND function; 0/1 for 1/2
motor. If 1 motor, then look to Motor OR input for selected motor.
Behavior defined by Z1-11)
29: Motor 1 Overload Contact. When input is open, declare an
OL Fault, issue an EF0 fault to the drive, delay per EF0 Fault
DI-5 Func Sel
Delay Time (Z1-30), and open Drive Output (K2) and Bypass
(K3) contactors.
30: Motor 2 Overload Contact. When input is open, declare an
OL Fault, issue an EF0 fault to the drive, delay per EF0 Fault
Delay Time (Z130), and open Drive Output (K2) and Bypass
(K3) contactors.
31: HAND Select
32: AUTO Select
DI-6 Func Sel
33: DRIVE/BYPASS Select (0/1 for Drive/Bypass)
34: Fault Reset
35: External Fault (EF0)
DI-7 Func Sel
36: External Fault (EFB)
37: Run Reverse
DI-8 Func Sel
0: Normal. Lack of input signal = OFF
DI-1 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
DI-2 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
DI-3 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
DI-4 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
DI-5 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
DI-6 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
0: Normal. Lack of input signal = OFF
DI-7 Invert
1: Inverted. Lack of input signal = ON
0: Normal
1: Inverted
Description
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Values
Page
Default: 21
187
Range: 0 to 37
Default: 22
187
Range: 0 to 37
Default: 23
187
Range: 0 to 37
Default: 24
187
Range: 0 to 37
Default: 25
187
Range: 0 to 37
Default: 0
187
Range: 0 to 37
Default: 0
187
Range: 0 to 37
Default: 29
187
Range: 0 to 37
Default: 0
189
Range: 0, 1
Default: 0
189
Range: 0, 1
Default: 0
189
Range: 0, 1
Default: 0
189
Range: 0, 1
Default: 0
189
Range: 0, 1
Default: 0
189
Range: 0, 1
Default: 0
189
Range: 0, 1

Advertisement