A.2 Drive Specifications
Note:
1. Perform rotational Auto-Tuning to obtain the performance specifications given below.
2. For optimum performance life of the drive, install the drive in an environment that meets the required specifications.
Item
Control Method
Frequency Control Range
Frequency Accuracy
(Temperature Fluctuation)
Frequency Setting Resolution
Output Frequency Resolution 0.001 Hz
Frequency Setting Signal
Starting Torque
Control
Speed Control Range
Character-
Speed Control Accuracy
istics
Accel/Decel Time
Braking Torque
V/f Characteristics
Main Control Functions
Power Supply Regeneration Available
Motor Protection
Momentary Overcurrent
Protection
Overload Protection
Overvoltage Protection
Protection
Undervoltage Protection
Functions
Momentary Power Loss
Ride-Thru
Heatsink Overheat Protection Thermistor
Stall Prevention
Ground Protection
Charge LED of Capacitor for
Control Power Supply
Area of Use
Ambient Temperature
Environment
Humidity
Storage Temperature
Altitude
Standard
Protection Design
<1> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<2> Actual specifications may vary depending on motor characteristics.
<3> Use a separate Momentary Power Loss Ride-Thru Unit if the application needs to continue running for up to 2 s during momentary power loss.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
V/f Control (V/f)
0.01 to 400 Hz
Digital input: within ±0.01% of the max output frequency (-10 to +40 °C)
Analog input: within ±0.1% of the max output frequency (25 °C ±10 °C)
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)
Main speed frequency reference: DC -10 to +10 V (20 kΩ), DC 0 to +10 V (20 kΩ),
4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
150% at 3 Hz
1:40
V/f: ±0.2 to 3% (25 °C ±10 °C)
0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Same value as overload tolerance in motoring or regeneration.
User-selected programs and V/f preset patterns possible
Momentary Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque Detection, 4 Step Speed
(max), Accel/Decel Switch, S-curve Accel/decel, 3-Wire Sequence, Auto-Tuning (Stationary for Line-
to-Line Resistance, Rotational for V/f Control), Cooling Fan on/off Switch, Slip Compensation, Torque
Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference, DC Injection Braking
at Start and Stop, Overexcitation Braking, PID Control (with sleep function), Energy Saving Control,
APOGEE FLN Comm. (RS-422/RS-485 4.8 kbps), BACnet Comm. (RS-485 max. 76.8 kbps),
MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), Metasys N2 Comm. (RS-422/RS-485
9.6 kbps), Fault Restart, Application Presets, Overexcitation Deceleration, Sequence Timer Operation,
Secondary PI Control, Bypass Operation, HOA Keypad, Dynamic Noise Control
Thermal overload relay
Drive stops when output current reaches about 200% of the rated current
Drive stops after 60 s at 120% of rated output current
208 V: Stops when input voltage exceeds approx. 315 V
480 V: Stops when input voltage exceeds approx. 630 V
208 V: Stops when input voltage falls below approx. 150 V
480 V: Stops when input voltage falls below approx. 300 V
Immediately stop after 2 ms or longer power loss
Continuous operation during power loss than 2 s (standard)
Stall Prevention is available during acceleration, deceleration, and during run.
<4>
Electronic circuit protection
Remains lit until control power supply voltage falls below 50 V
Indoors
IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
95 RH% or less (no condensation)
-20 °C to +60 °C (short-term temperature during transportation)
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
UL508A
IP20/NEMA Type 1 enclosure
A.2 Drive Specifications