YASKAWA Z1000U Technical Manual page 414

Low harmonic drive bypass for hvac applications
Hide thumbs Also See for Z1000U:
Table of Contents

Advertisement

F.6 Metasys N2 Point Database
u
Metasys N2 Analog Output (AO) Summary
Object ID
Object Name
AO 1
Speed Command
AO 2
Acceleration Time
AO 3
Deceleration Time
AO 4
PID Proportional Gain
AO 5
PID Integral Time
AO 6
Stall Prevention Level – Run
AO 7
Stall Prevention Level – Accel
AO 8
Frequency Reference Selection
AO 9
Run Command Selection
AO 10
PID Mode Select
AO 11
Frequency Command Upper Limit
AO 12
Frequency Command Lower Limit
AO 13
Motor Rated Current
AO 14
Jump Frequency 1
AO 15
Jump Frequency 2
AO 16
Jump Frequency 3
AO 17
Jump Frequency Bandwidth
AO 18
Number of Auto Restarts
AO 19
Operator Display Mode
AO 20
Power Loss Ride-Thru
AO 21
Cable Loss Timeout
AO 22
Cable Loss Speed
AO 23
PID Integral Limit
AO 24
PID Upper Limit Value
AO 25
PID Offset Adjustment
AO 26
PID Primary Delay Time
PID Feedback Reference Missing
AO 27
Detection Select
PID Feedback Reference Missing
AO 28
Detection Level
PID Feedback Reference Missing
AO 29
Detection Time
AO 30
Read Parameter Number
AO 31
Write Parameter Number
AO 32
Write Parameter Data
u
Metasys N2 Binary Input (BI) Summary
Object ID
Object Name
BI 1
Run/Stop Monitor
BI 2
Forward/Reverse Monitor
BI 3
Drive Ready Monitor
BI 4
Fault Monitor
BI 5
Zero Speed
BI 6
Speed Agree
BI 7
Minor Fault
BI 8
Major Fault
BI 9
Drive Communication Error Monitor
414
Table F.6 Metasys N2 Analog Output Summary (Bypass to Metasys N2)
Units
0.01 Hz
seconds
seconds
seconds
% of Max
% of Max
0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz
seconds
seconds
0.01 Hz
0.1%
0.1
0.1
0.01
1%
0.1 s
Table F.7 Metasys N2 Binary Input Summary (Bypass to Metasys N2)
Default
0
0
0
0
0
0
0
0
0
Default Value
30.0
30.0
2.00
5.0
%
120
%
120
0
1
0
100.0
0.0
A
Motor model dependent
0.0
0.0
0.0
1.0
0
0
Drive model dependent
2.0
0.00
100.0
100.0
0.0
0.00
1
0
0
1.0
Off (0) State
Stopped
Forward
Not Ready
Not Faulted
Not Zero Speed
Not Speed Agree
No Minor Fault
No Major Fault
No Error
YASKAWA SIEP YAIZ1D 01C Z1000U HVAC MATRIX Drive Bypass Technical Manual
Bypass Parameter
C1-01
C1-02
b5-02
b5-03
L3-06
L3-02
Z1-07
Z1-08
b5-01
d2-01
d2-02
E2-01
d3-01
d3-02
d3-03
d3-04
L5-01
o1-03
L2-02
Z3-06
Z3-10
b5-04
b5-06
b5-07
b5-08
b5-12
b5-13
b5-14
On (1) State
Running
Reverse
Ready
Faulted
Zero Speed
Speed Agree
Minor Fault
Major Fault
Error

Advertisement

Table of Contents
loading

Table of Contents