VFD2 Nominal Motor HPwr (N.PWR)
This configuration defines the nominal motor power. This value
must equal the value of the combined HP of both motors. Motor
HP is found on the motor rating plate. Power to the VFD must be
cycled in order for a change to this configuration to take effect.
VFD2 Motor Direction (M.DIR)
This configuration sets the direction of motor rotation. Motor di-
rection change occurs immediately upon a change to this configu-
ration. Power to the VFD need NOT be cycled for a change to this
configuration to take effect.
VFD2 Acceleration Time (ACCL)
This configuration sets the acceleration time from zero to maxi-
mum output frequency. Power to the VFD must be cycled in order
for a change to this configuration to take effect.
VFD2 Deceleration Time (DECL)
This configuration sets the deceleration time from maximum out-
put frequency to zero. Power to the VFD must be cycled in order
for a change to this configuration to take effect.
VFD2 Switching Frequency (SW.FQ)
This configuration sets the switching frequency for the drive.
Power to the VFD must be cycled in order for a change to this
configuration to take effect.
VFD2 Type (TYPE)
This configuration sets the type of VFD communication. This
configuration should not be changed without first consulting a
Carrier service engineering representative.

Remote Control Switch Input

The remote switch input is located on the RXB board and connect-
ed to TB201 terminals 3 and 4. The switch can be used for several
remote control functions. See Table 83.
Table 83 — Remote Switch Configuration
ITEM
EXPANSION
REMT
Remote Input State
RM.CF Remote Switch Config
RMI.L
RemSw Off-Unoc-Strt-NoOv
REMOTE
SWITCH LOGIC
SWITCH
CONFIGURATION
STATUS
(RMI.L)
OPEN
OPEN
CLOSED
OPEN
CLOSED
CLOSED
RANGE
UNITS
CCN POINT
ON/OFF
RMTIN
0 to 3
RMTINCFG
Open/Close
RMTINLOG
Table 84 — Remote Switch Logic Configuration
REMOTE INPUT STATE
(REMT)
OFF (0)
ON (1)
ON (0)
OFF (1)
Remote Input State (Inputs
This is the actual real time state of the remote input.
Remote Switch Config (Configuration
This is the configuration that allows the user to assign different
types of functionality to the remote discrete input.
0 — NO REMOTE SW — Remote switch will not be used.
1 — OCC-UNOCC SW — The remote switch input will con-
trol the occupancy state. When the remote switch input is ON,
the unit is forced into the occupied mode. When the remote
switch is OFF, the unit is forced into the unoccupied mode.
2 — STRT/STOP — The remote switch input will start
and stop the unit. When the unit is commanded to stop, any
timeguards in place on compressors will be honored first.
When the remote switch is ON, the unit will be command-
ed to stop. When the remote switch is OFF, the unit will be
enabled to operate.
3 — OVERRIDE SW — The remote switch can be used to
override any internal or external time schedule being used
by the control and force the unit into an occupied mode
when the remote input state is ON. When the remote
switch is ON, the unit will be forced into an occupied state.
When the remote switch is OFF, the unit will use its inter-
nal or external time schedules.
Remote Switch Logic Configuration (Configuration
SW.LG
RMI.L)
The control allows for configuration of a normally open/closed
status of the remote input switch via RMI.L. If this variable is
configured OPEN, then when the switch is open, the remote in-
put switch perceives the logic state as OFF. Correspondingly, if
RMI.L is set to CLOSED, the remote input switch will perceive
a closed switch as meaning OFF. See Table 84.
REMOTE SWITCH CONFIGURATION (RM.CF)
0
No Remote Switch
Occ-Unocc Switch
xxxxx
Unoccupied
xxxxx
Occupied
xxxxx
Occupied
xxxxx
Unoccupied
103
GEN.I
REMT)
UNIT
RM.CF)
1
2
Start/Stop
Start
No Override
Stop
Stop
Start
No Override

3
Override
Override
Override