POINT DESCRIPTION
Air Temp Lvg Supply Fan
Airside Linkage Alarm
Airside Linkage Status
Alarm State
Building Pressure
Building Pressure Setp.
Cir A Discharge Pressure
Cir A Sat. Condensing Temperature
Cir A Sat. Suction Temperature
Cir A Suction Pressure
Cir B Discharge Pressure
Cir B Sat. Condensing Temperature
Cir B Sat. Suction Temperature
Cir B Suction Pressure
Compressor A1 Relay
Compressor A2 Relay
Compressor A3 Relay
Compressor B1 Relay
Compressor B2 Relay
Compressor B3 Relay
Controlling Return Air Temp
Controlling Space Temp
Controlling Static Pressure Setpoint
Cooling Control Point
Cooling Occupied Setpoint
Cooling Unoccupied Setpoint
Ctl.Temp RAT,SPT or ZONE - Prime Variable
Current Running Capacity
Current Running Capacity (Heat)
Dehumidify Cool Setpoint
Dehumidify Input
Dehumidify RH Setpoint
Demand Limit Sw.1 Setpt.
Demand Limit Sw.2 Setpt.
Demand Limit Switch 1
Demand Limit Switch 2
Economizer Act. Curr. Pos
Economizer Active?
EDT Sensor Bad?
Element Comm Status
Element Communications Alarm
Equipment Touch reset linkage Alarm
Evaporator Discharge Tmp
Exhaust Fan VFD Speed
Filter Status Input
Heat Relay 1
Heat Relay 2
Heat-Cool Setpoint Gap
Heating Control Point
Heating Occupied Setpoint
Heating Supply Air Setpt
Heating Unoccupied Setpoint
Ht.Coil Command Position
HumidiMizer 3-way Valve
HumidiMizer Capacity
HVAC Mode Numerical Form
IAQ - Discrete Input
IAQ - PPM Return CO2
Indoor Air Quality
Leaving Air Temperature
Linkage Max Damper Position
Local Schedule
APPENDIX G — UPC OPEN CONTROLLER (CONT)
NETWORK POINTS LIST
CCN POINT
READ/
NAME
WRITE
R
R
R
R
R
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R
R
R/W
R/W
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R/W
R
R
R/W
R
R
R/W
R
R/W
R/W
R/W
R
R
R
R
R/W
R/W
R
R
R
R
DEFAULT
UNITS
RANGE
VALUE
°F
0 = NORMAL
1 = ALARM
0 = Not Active
1 = Active
0 = NORMAL
1 = ALARM
H2O
H2O
–0.25 to 0.25
psig
°F
°F
psig
psig
°F
°F
psig
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
°F
–40 to 240
°F
–40 to 240
inH2O
°F
°F
40 to 99
°F
40 to 110
°F
%
%
°F
40 to 55
0 = OFF; 1 = ON
%
10 to 90
%
0 to 100
%
0 to 100
0 = OFF; 1 = ON
0 = OFF; 1 = ON
%
0 = NO; 1 = YES
0 = NO; 1 = YES
0 = No Comm
1 = Normal
0 = Comm Normal
1 = Comm Lost
0 = NO; 1 = YES
°F
%
0 = CLEAN; 1 = DIRTY
0 = OFF; 1 = ON
0 = OFF; 1 = ON
°^F
2-10
°F
°F
40 to 99
°F
80 to 120
°F
40 to 99
%
0 = OFF; 1 = ON
%
no unit
0 = LOW; 1 = HIGH
no unit
0 to 5000
ppm
°F
%
0 = OFF; 1 = ON
249
BACNET
BACNET OBJECT
OBJECT ID
NAME
AV:10
sat_1
BV:7030
air_linkage_fail_1
BV:2601
a_link_status_1
BV:9
alm_1
AV:1070
bldg_static_press_1
AV:3070
bldg_press_stpt_1
AV:1601
discharge_press_a_1
AV:1602
sat_cond_temp_a_1
AV:1603
sat_suction_temp_a_1
AV:1600
suction_press_a_1
AV:1605
discharge_press_b_1
AV:1606
sat_cond_temp_b_1
AV:1607
sat_suction_temp_b_1
AV:1604
suction_press_b_1
BV:16
cmpa1_1
BV:17
cmpa2_1
BV:13
cmpa3_1
BV:18
cmpb1_1
BV:19
cmpb2_1
BV:14
cmpb3_1
AV:1030
ra_temp_1
AV:2007
space_temp_1
AV:3055
ct_sa_static_stpt_1
AV:1024
cool_ctrl_point_1
AV:3001
occ_cl_stpt_1
AV:3003
unocc_cl_stpt_1
AV:43
ctrltemp_1
AV:1023
cool_capacity_1
AV:44
htsg_cap_1
AV:49
dhcoolsp_1
BV:30
dhdiscin_1
AV:50
dhrelhsp_1
AV:53
dlswsp1_1
AV:54
dlswsp2_1
BV:1006
dmd_sw1_1
BV:1007
dmd_sw2_1
AV:1028
econ_pos_1
BV:36
ecactive_1
BV:44
edt_stat_1
BV:2999
element_stat_1
BV:105
comm_lost_alm_1
BV:5123
et_reset_as_link_1
AV:76
edt_1
AV:2075
ef_vfd_output_1
BV:1052
filter_status_1
BV:52
hs1_1
BV:53
hs2_1
AV:83
hcsp_gap_1
AV:1025
heat_ctrl_point_1
AV:3002
occ_ht_stpt_1
AV:3008
saspheat_1
AV:3004
unocc_ht_stpt_1
AV:55
htclcpos_1
BV:47
hum3wval_1
AV:57
hmzrcapc_1
AV:1022
hvac_mode_1
BV:1050
iaq_status_1
AV:1009
iaq_1
AV:2607
link_iaq_1
AV:1027
lvg_air_temperature_1
AV:2611
link_max_dmpr_1
BV:5
schedule_1