Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 51

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
COOL
COOLING CONFIGURATION
A1.EN
Enable Compressor A1
A2.EN
Enable Compressor A2
A3.EN
Enable Compressor A3
B1.EN
Enable Compressor B1
B2.EN
Enable Compressor B2
B3.EN
Enable Compressor B3
CS.A1
CSB A1 Feedback Alarm
CS.A2
CSB A2 Feedback Alarm
CS.A3
CSB A3 Feedback Alarm
CS.B1
CSB B1 Feedback Alarm
CS.B2
CSB B2 Feedback Alarm
CS.B3
CSB B3 Feedback Alarm
Z.GN
Capacity Threshold Adjst
MC.LO
Compressor Lockout Temp
LLAG
Lead/Lag Operation?
M.M.
Motor Master Control?
SCT.H
Maximum Condenser Temp
SCT.L
Minimum Condenser Temp
DG.A1
A1 is Digital Scroll
MC.A1
A1 Min Digital Capacity
DS.AP
Dig Scroll Adjust Delta
DS.AD
Dig Scroll Adjust Delay
DS.RP
Dig Scroll Reduce Delta
DS.RD
Dig Scroll Reduce Delay
DS.RO
Dig Scroll Reduction OAT
DS.MO
Dig Scroll Max Only OAT
MLV
Min Load Valve Enable
H.SST
Hi SST Alert Delay Time
RR.VF
Rev Rotation Verified?
CS.HP
Use CSBs for HPS Detect?
LASP
Low Ambient Set Point
OV.DB
Outdoor VFD SCT DeadBand
OV.RH
Outdoor VFD Dehum-RH SPD
LAST OV
MinStartSpeed Low Amb
OV.EN
Outdoor VFD Enable
ODV.A
OUTDOOR VFD-A CONFIGS
N.VLT
OV-A Nominal Motor Volts
N.AMP
OV-A Nominal Motor Amps
N.FRQ
OV-A Nominal Motor Freq
N.RPM
OV-A Nominal Motor rpm
N.PWR
OV-A Nominal Motor HPwr
OV-A Motor Direction
M.DIR
0=FORWARD, 1=REVERSE
ACCL
OV-A Acceleration Time
DECL
OV-A Deceleration Time
SW.FQ
OV-A Switching Frequency
ODV.B
OUTDOOR VFD-B CONFIGS
N.VLT
OV-B Nominal Motor Volts
N.AMP
OV-B Nominal Motor Amps
N.FRQ
OV-B Nominal Motor Freq
N.RPM
OV-B Nominal Motor rpm
N.PWR
OV-B Nominal Motor HPwr
OV-B Motor Direction
M.DIR
0=FORWARD, 1=REVERSE
ACCL
OV-B Acceleration Time
DECL
OV-B Deceleration Time
SW.FQ
OV-B Switching Frequency
O.PID
OUTDOOR VFD PID CONFIGS
OV.RR
Outdoor VFD PI Run Rate
OV.PG
Outdoor VFD Prop. Gain
OV.TI
Outdoor VFD Integ. Time
OV.AU
Outdoor VFD Anti-Windup
LA.PG
OV Prop. Gain at Low Amb
LA.TI
OV Intg. Time at Low Amb
Table 37 — Cooling Configuration
EXPANSION
RANGE
UNITS
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
0.1 to 10.0
–25 to 55
dF
Yes/No
Yes/No
100 to 150
dF
40 to 90
dF
Yes/No
10 to 100
%
0 to 100
%
15 to 60
sec
0 to 100
%
15 to 60
sec
70 to 120
dF
70 to 120
dF
Enable/Disable
5 to 30
min
Yes/No
Yes/No
70 to 150
dF
0 to 20
dF
0 to 100
%
0 to 100
%
No/Yes
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
0 to 1800
0 to 1800
0 to 3
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
OVB_MDIR
0 to 1800
0 to 1800
0 to 3
5 to 120
0 to 5
0.5 to 200
0.1 to 1
0 to 5
0.5 to 200
51
CCN POINT
DEFAULT
CMPA1ENA
Enable
CMPA2ENA
Enable
CMPA3ENA
Enable
CMPB1ENA
Enable
CMPB2ENA
Enable
CMPB3ENA
Enable
CSB_A1EN
Enable
CSB_A2EN
Enable
CSB_A3EN
Enable
CSB_B1EN
Enable
CSB_B2EN
Enable
CSB_B3EN
Enable
Z_GAIN
1
OATLCOMP
53
LLENABLE
No
MOTRMAST
No
SCT_MAX
115
SCT_MIN
72
DIGCMPA1
No
MINCAPA1
50
DSADJPCT
100
DSADJDLY
20
DSREDPCT
6
DSREDDLY
30
DSREDOAT
95
DSMAXOAT
105
MLV_ENAB
Disable
HSSTTIME
10
REVR_VER
No
CSbhpDET
Yes
LASP
100
OV_SCTDB
2
OV_RH
50
OV_STMIN
12
OV_ENA
OVA_NVLT
OVA_NAMP
OVA_NFRQ
OVA_Nrpm
OVA_NPWR
OVA_MDIR
OVA_ACCL
OVA_DECL
OVA_SWFQ
OVB_NVLT
OVB_NAMP
OVB_NFRQ
OVB_Nrpm
OVB_NPWR
OVB_ACCL
OVB_DECL
OVB_SWFQ
OV_RATE
OV_PG
OV_TI
OV_AU
OV_PG_LA
OV_TI_LA