Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 213

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

TABLE
EC_DIAG
GSINPUTS
APPENDIX B — CCN TABLES (CONT)
Table P — MAINTENANCE DISPLAY TABLES (cont)
DISPLAY NAME
Economizer Active?
Conditions which prevent
economizer being active:
Econ Act. Unavailable?
Econ 2 Act. Unavailable?
Enth.Switch Read High?
DBC - OAT lockout?
DEW - OA Dewpt. lockout?
DDBC- OAT > RAT lockout?
OAEC- OA Enth Lockout?
DEC - Diff.Enth.Lockout?
EDT Sensor Bad?
OAT Sensor Bad?
Economizer forced?
Supply Fan not on 30s?
Cool Mode not in effect?
OAQ lockout in effect?
Econ recovery hold off?
Dehumid. Disabled Econ.?
Outside Air Temperature
OutsideAir DewPoint Temp
Outside Air Rel.Humidity
Outdoor Air Enthalpy
Return Air Temperature
Return Air Rel.Humidity
Return Air Enthalpy
High OAT Lockout Temp
Econ ChangeOver Select
OA Enthalpy ChgOvr Selct
Outdr.Enth Compare Value
OA Dewpoint Temp Limit
Supply Fan Relay
Economizer Act.Cmd.Pos.
Economizer Act.Curr.Pos.
Economzr 2 Act.Curr.Pos.
Evaporator Discharge Tmp
Economizer Control Point
EDT Trend in degF/minute
Economizer Prop.Gain
Economizer Range Adjust
Economizer Speed Adjust
Economizer Deadband
Economizer Timer
Low Ambient Setpoint
Head Pressure Setpoint
HVAC Mode Numerical Form
Outside Air Temperature
Cir A Sat.Suction Temp
Cir B Sat.Suction Temp
Cir A Discharge Pressure
Cir B Discharge Pressure
Cir A Sat.Condensing Tmp
Cir B Sat.Condensing Tmp
Circuit-A Capacity
Circuit-B Capacity
Percent Available Cap. A %
Percent Available Cap. B %
Compressor A1 Relay
Compressor A2 Relay
Compressor B1 Relay
Compressor B2 Relay
Any A-comp running?
Any B-comp running?
Circuit A Reheat Enable?
Circuit B Reheat Enable?
CircuitA Reheat Running?
CircuitB Reheat Running?
HMZR Reheat Active Mode?
Circuit A Scroll Enable?
Circuit B Scroll Enable?
Circuit A Scroll Active?
Circuit B Scroll Active?
HPSP Forced flag
OV MinStartSpeed Low Amb
FanStartSpeed Forced Ena
RANGE
UNITS
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
dF
dF
%
dF
%
dF
dF
%
%
%
dF
dF
^F
^F
^F
sec
80-150
degF
70-150
degF
degF
degF
degF
PSIG
PSIG
degF
degF
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
%
No/Yes
213
POINT NAME
WRITE STATUS
ECACTIVE
ECONUNAV
ECN2UNAV
ENTH
DBC_STAT
DEW_STAT
DDBCSTAT
OAECSTAT
DEC_STAT
EDT_STAT
OAT_STAT
ECONFORC
SFONSTAT
COOL_OFF
OAQLOCKD
ECONHELD
DHDISABL
OAT
forcible
OADEWTMP
OARH
forcible
OAE
RAT
forcible
RARH
forcible
RAE
OAT_LOCK
config
ECON_SEL
config
OAEC_SEL
config
OAEN_CFG
config
OADEWCFG
config
SFAN
ECONOCMD
forcible
ECONOPOS
ECON2POS
EDT
ECONCPNT
EDTTREND
EC_PGAIN
config
EC_RANGE
config
EC_SPEED
config
EC_DBAND
config
ERATETMR
config
LASP
100
HPSP
110
MODEHVAC
OAT
SSTA
SSTB
DP_A
DP_B
SCTA
SCTB
CIRCACAP
CIRCBCAP
CAPA_A
CAPB_A
CMPA1
CMPA2
CMPB1
CMPB2
ANY_ARUN
ANY_BRUN
A_RH_ENA
B_RH_ENA
A_RH_RUN
B_RH_RUN
HZRHACTV
DSA_ENAB
DSB_ENAB
DSA_ACTV
DSB_ACTV
HPSP_FRC
OV_STMIN
OVST_FRC