TABLE
ACTUATOR
Econ Serial Number 1
Econ Serial Number 2
Econ Serial Number 3
Econ Serial Number 4
Econ Ctrl Angle Lo Limit
Econ 2 Serial Number 1
Econ 2 Serial Number 2
Econ 2 Serial Number 3
Econ 2 Serial Number 4
Econ 2 Ctrl Angle Lo Limit
Humd Serial Number 1
Humd Serial Number 2
Humd Serial Number 3
Humd Serial Number 4
Humd Ctrl Angle Lo Limit
Hydronic Ht.Serial Number 1
Hydronic Ht.Serial Number 2
Hydronic Ht.Serial Number 3
Hydronic Ht.Serial Number 4
Hydr.Ht. Ctrl Angle Lo Limit
BP 1 Serial Number 1
BP 1 Serial Number 2
BP 1 Serial Number 3
BP 1 Serial Number 4
BP 1 Ctrl Angle Lo Limit
BP 2 Serial Number 1
BP 2 Serial Number 2
BP 2 Serial Number 3
BP 2 Serial Number 4
BP 2 Ctrl Angle Lo Limit
ALLM
SPT lo alert limit/occ
SPT hi alert limit/occ
SPT lo alert limit/unocc
SPT hi alert limit/unocc
EDT lo alert limit/occ
EDT hi alert limit/occ
EDT lo alert limit/unocc
EDT hi alert limit/unocc
RAT lo alert limit/occ
RAT hi alert limit/occ
RAT lo alert limit/unocc
RAT hi alert limit/unocc
OAT lo alert limit
OAT hi alert limit
RARH low alert limit
RARH high alert limit
OARH low alert limit
OARH high alert limit
SP low alert limit
SP high alert limit
BP lo alert limit
BP high alert limit
IAQ high alert limit
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES
DISPLAY NAME
RANGE
UNITS
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 9999
0 to 6
0 to 9999
0 to 254
–10 to 245
dF
–10 to 245
dF
–10 to 245
dF
–10 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
–40 to 245
dF
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 5
"H2O
0 to 5
"H2O
–0.25 to 0.25
"H2O
–0.25 to 0.25
"H2O
0 to 5000
204
POINT NAME
DEFAULT
ECON_SN1
0
ECON_SN2
0
ECON_SN3
0
ECON_SN4
0
ECONCALM
ECN2_SN1
0
ECN2_SN2
0
ECN2_SN3
0
ECN2_SN4
0
ECN2CALM
HUMD_SN1
0
HUMD_SN2
0
HUMD_SN3
0
HUMD_SN4
0
HUMDCALM
HTCL_SN1
0
HTCL_SN2
0
HTCL_SN3
0
HTCL_SN4
0
HTCLCALM
BP1_SN1
0
BP1_SN2
0
BP1_SN3
0
BP1_SN4
0
BP1CALM
BP2_SN1
0
BP2_SN2
0
BP2_SN3
0
BP2_SN4
0
BP2CALM
SPLO
60
SPHO
85
SPLU
45
SPHU
100
SALO
40
SAHO
100
SALU
40
SAHU
100
RALO
60
RAHO
90
RALU
40
RAHU
100
OATL
–40
OATH
150
RRHL
0
RRHH
100
ORHL
0
ORHH
100
SPL
0
SPH
2
BPL
–0.25
BPH
0.25
IAQH
1200