Dirty Sensor Test; Changing The Dirt Sensor Test; Remote Station Test; Sd-Trk4 Remote Alarm Test Procedure - Carrier 48FC M20 Series Service And Maintenance Instructions

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 17.5-27.5 nominal tons
Table of Contents

Advertisement

IMPORTANT: Failure to follow this ALERT can result in
an unnecessary evacuation of the facility.
Pressing the controller's test/reset switch for longer than seven
seconds will put the duct detector into the alarm state and
activate all automatic alarm responses.
DIRTY CONTROLLER TEST PROCEDURE
1.
Press the controller's test/reset switch for two seconds.
2.
Verify that the controller's Trouble LED flashes.

Dirty Sensor Test

The dirty sensor test provides an indication of the sensor's ability
to compensate for gradual environmental changes. A sensor that
can no longer compensate for environmental changes is consid-
ered 100% dirty and requires cleaning or replacing. A field pro-
vided SD-MAG test magnet must be used to initiate a sensor dirty
test. The sensor's Dirty LED indicates the results of the dirty test
as shown in Table 2.
IMPORTANT: Failure to follow this ALERT can result in
an unnecessary evacuation of the facility.
Holding the test magnet against the sensor housing for more
than seven seconds will put the duct detector into the alarm
state and activate all automatic alarm responses.
Table 2 — Dirty LED Test
FLASHES
1
0-25% dirty. (Typical of a newly installed detector)
2
3
4
DIRTY SENSOR TEST PROCEDURE
1.
Hold the test magnet where indicated on the side of the
sensor housing for two seconds.
2.
Verify that the sensor's Dirty LED flashes.
IMPORTANT: Failure to follow this ALERT can result in
an unnecessary evacuation of the facility.
Changing the dirty sensor test operation will put the detector
into the alarm state and activate all automatic alarm responses.
Before changing dirty sensor test operation, disconnect all
auxiliary equipment from the controller and notify the proper
authorities if connected to a fire alarm system.

Changing the Dirt Sensor Test

By default, sensor dirty test results are indicated by:
The sensor's Dirty LED flashing.
The controller's Trouble LED flashing.
The controller's supervision relay contacts toggle.
The operation of a sensor's dirty test can be changed so that the
controller's supervision relay is not used to indicate test results.
When two detectors are connected to a controller, sensor dirty test
operation on both sensors must be configured to operate in the
same manner.
TO CONFIGURE THE DIRTY SENSOR TEST OPERATION
1.
Hold the test magnet where indicated on the side of the
sensor housing until the sensor's Alarm LED turns on and
its Dirty LED flashes twice (approximately 60 seconds).
2.
Reset the sensor by removing the test magnet then holding
it against the sensor housing again until the sensor's Alarm
LED turns off (approximately 2 seconds).
DESCRIPTION
25-50% dirty
51-75% dirty
76-99% dirty

Remote Station Test

The remote station alarm test checks a test/reset station's ability to
initiate and indicate an alarm state.
IMPORTANT: Failure to follow this ALERT can result in
an unnecessary evacuation of the facility.
This test places the duct detector into the alarm state. Unless
part of the test, disconnect all auxiliary equipment from the
controller before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper authorities
before performing the test.

SD-TRK4 Remote Alarm Test Procedure

1.
Turn the key switch to the RESET/TEST position for
seven seconds.
2.
Verify that the test/reset station's Alarm LED turns on.
3.
Reset the sensor by turning the key switch to the
RESET/TEST position for two seconds.
4.
Verify that the test/reset station's Alarm LED turns off.

Remote Test/Reset Station Dirty Sensor Test

The test/reset station dirty sensor test checks the test/reset station's
ability to initiate a sensor dirty test and indicate the results. It must
be wired to the controller as shown in Fig. 42 and configured to
operate the controller's supervision relay. For more information,
see "Dirty Sensor Test" on page 33.
12
1
TB3
1
3
14
Supervision
Relay
Contacts [3]
13
19
Wire must be
added by
15
installer
20
Fig. 42 — Remote Test/Reset Station Connections
IMPORTANT: Failure to follow this ALERT can result in
an unnecessary evacuation of the facility.
If the test/reset station's key switch is left in the RESET/TEST
position for longer than seven seconds, the detector will
automatically go into the alarm state and activate all automatic
alarm responses.
33
Smoke Detector
Controller
Auxiliary
Equipment
+
2
SD-TRM4
Trouble
5
Power
18 VDC (-)
4
Alarm
1
Reset/Test
2
3
18 VDC (-)
2

Advertisement

Table of Contents
loading

Table of Contents