ITEM
VIEW
AUTO VIEW OF RUN STATUS
HVAC
ascii string spelling out the hvac modes
OCC
Occupied?
MAT
Mixed Air Temperature
EDT
Evaporator Discharge Tmp
LAT
Leaving Air Temperature
EC.C.P
Economizer Control Point
ECN.P
Economizer Act.Curr.Pos.
EC2.P
Economzr2 Act.Curr.Pos.
CL.C.P
Cooling Control Point
C.CAP
Current Running Capacity
CL.ST
Requested Cool Stage
HT.C.P
Heating Control Point
HT.ST
Requested Heat Stage
H.MAX
Maximum Heat Stages
ITEM
ECON
ECONOMIZER RUN STATUS
ECN.P
Economizer Act.Curr.Pos.
EC2.P
Economzr2 Act.Curr.Pos.
ECN.C
Economizer Act.Cmd.Pos.
ACTV
Economizer Active?
DISA
ECON DISABLING CONDITIONS
UNV.1
Econ Act. Unavailable?
UNV.2
Econ2 Act. Unavailable?
ENTH
Enth. Switch Read High?
DBC
DBC - OAT Lockout?
DEW
DEW - OA Dewpt.Lockout?
DDBC
DDBD- OAT > RAT Lockout?
OAEC
OAEC- OA Enth Lockout?
DEC
DEC - Diff.Enth.Lockout?
EDT
EDT Sensor Bad?
OAT
OAT Sensor Bad?
FORC
Economizer Forced?
SFON
Supply Fan Not On 30s?
CLOF
Cool Mode Not In Effect?
OAQL
OAQ Lockout in Effect?
HELD
Econ Recovery Hold Off?
DH.DS
Dehumid. Disabled Econ.?
O.AIR
OUTSIDE AIR INFORMATION
OAT
Outside Air Temperature
OA.RH
Outside Air Rel. Humidity
OA.E
Outside Air Enthalpy
OA.D.T
OutsideAir Dewpoint Temp
Table 97 — Auto View of Run Status Display Table
EXPANSION
Table 98 — Economizer Run Status Display Table
EXPANSION
RANGE
UNITS
YES/NO
dF
dF
dF
dF
0 to 100
%
0 to 100
%
dF
dF
RANGE
UNITS
0 to 100
%
0 to 100
%
0 to 100
%
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
dF
%
dF
119
CCN POINT
WRITE STATUS
string
OCCUPIED
forcible
MAT
EDT
LAT
ECONCPNT
ECONOPOS
ECON2POS
COOLCPNT
CAPTOTAL
CL_STAGE
HEATCPNT
HT_STAGE
HTMAXSTG
CCN POINT
WRITE STATUS
ECONOPOS
ECON2POS
ECONOCMD
forcible
ECACTIVE
ECONUNAV
ECN2UNAV
ENTH
DBC_STAT
DEW_STAT
DDBCSTAT
OAECSTAT
DEC_STAT
EDT_STAT
OAT_STAT
ECONFORC
SFONSTAT
COOL_OFF
OAQLOCKD
ECONHELD
DHDISABL
OAT
forcible
OARH
forcible
OAE
OADEWTMP