Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 250

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

POINT DESCRIPTION
Maximum Damper Position
Maximum Reset
Minimum Damper Position
Mixed Air Temperature
OAQ - PPM Outdoor CO2
Occupied Cool Mode End
Occupied Cool Mode Start
Occupied Heat Mode End
Occupied Heat Mode Start
Occupied?
Outside Air CFM
Outside Air Relative Humidity
Outside Air Temperature
Power Exhaust Relay 1
Power Exhaust Relay 2
Relay 3 W1 Gas Valve 2
Relay 4 W2 Gas Valve 2
Relay 5 W1 Gas Valve 3
Relay 6 W2 Gas Valve 3
Requested Heat Stage
Return Air CFM
Return Air Relative Humidity
Return Air Temperature
Setpoint Adjustment Enable
SP High Alert Limit
SP Low Alert Limit
Space Relative Humidity
Space Relative Humidity
Space Temp Offset Range
Space Temperature
Staged Gas LAT 1
Staged Gas LAT 2
Staged Gas LAT 3
Static Pressure
Static Pressure Reset
Static Pressure Reset Enable
Static Pressure Setpoint
Supply Air CFM
Supply Air Reset
Supply Air Setpnt. Reset
Supply Air Setpoint
Supply Fan Relay
Supply Fan Status Switch
Supply Fan VFD Speed
System Cooling Demand Level
System Demand Limiting
System Heating Demand Level
System OAT Master
System Space AQ
System Space RH
System Space Temperature
Thermostat G Input
Thermostat W1 Input
Thermostat W2 Input
Thermostat Y1 Input
Thermostat Y2 Input
Unoccupied Cool Mode End
Unoccupied Cool Mode Start
Unoccupied Heat Mode End
Unoccupied Heat Mode Start
Use Linkage
User Defined Analog 1
User Defined Analog 10
User Defined Analog 11
APPENDIX G — UPC OPEN CONTROLLER (CONT)
NETWORK POINTS LIST (CONT)
CCN POINT
READ/
NAME
WRITE
R/W
R/W
R/W
R
R/W
R
R
R
R
R/W
R
R/W
R/W
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R
R
R
R/W
R/W
R/W
R
R
R/W
R/W
R
R/W
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R/W
R/W
R/W
R/W
DEFAULT
UNITS
RANGE
VALUE
%
0 to 100
inH2O
%
0 to 100
°F
no unit
0 to 5000
°F
°F
°F
°F
0 = NO; 1 = YES
cfm
%
0 to 100
°F
–40 to 240
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
no unit
cfm
%
0 to 100
°F
–40 to 240
0 = DISABLE
1 = ENABLE
H2O
0 to 5
H2O
0 to 5
%
%
0 to 100
°^F
1 to 10
°F
–40 to 240
°F
°F
°F
H2O
no unit
0 to 15
0 = DISABLE
1 = ENABLE
H2O
0 to 5
cfm
0 = OFF; 1 = ON
°^F
0 to 20
°F
45 to 75
0 = OFF; 1 = ON
0 = OFF; 1 = ON
%
no unit
0 = Inactive
1 = Active
no unit
°F
ppm
%rh
°F
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
0 = OFF; 1 = ON
°F
°F
°F
°F
0 = NO; 1 = YES
no unit
no unit
no unit
250
BACNET
BACNET OBJECT
OBJECT ID
NAME
AV:3052
max_dmpr_pos_1
AV:3054
max_reset_1
AV:3053
min_dmpr_pos_1
AV:1500
ma_temp_1
AV:113
oaq_1
AV:114
occl_end_1
AV:115
occlstrt_1
AV:116
ocht_end_1
AV:117
ochtstrt_1
BV:2008
occ_status_1
AV:66
oacfm_1
AV:119
oarh_1
AV:1003
oat_1
BV:49
pe1_1
BV:51
pe2_1
BV:76
hs3_1
BV:77
hs4_1
BV:78
hs5_1
BV:79
hs6_1
AV:2003
heat_run_1
AV:69
racfm_1
AV:134
rarh_1
AV:135
rat_1
BV:6
stpt_adj_enable_1
AV:73
sph_1
AV:74
spl_1
AV:2606
link_rh_1
AV:72
sprh_1
AV:139
spto_rng_1
AV:137
spt_1
AV:150
lat1sgas_1
AV:151
lat2sgas_1
AV:152
lat3sgas_1
AV:1016
static_press_1
AV:157
spreset_1
BV:3051
st_pr_rst_en_1
AV:3050
sa_static_stpt_1
AV:78
sacfm_1
BV:93
modesars_1
AV:158
sasprset_1
AV:3007
sa_temp_stpt_1
BV:2001
sfan_1
BV:95
sfs_1
AV:2050
sf_vfd_output_1
AV:9006
cool_demand_level_1
BV:7
dem_lmt_act_1
AV:9036
heat_demand_level_1
AV:80001
mstr_oa_temp_1
AV:1903
system_aq_1
AV:1904
system_rh_1
AV:1902
system_spt_1
BV:1021
g_input_1
BV:1019
w1_input_1
BV:1020
w2_input_1
BV:1017
y1_input_1
BV:1018
y2_input_1
AV:168
uccl_end_1
AV:169
ucclstrt_1
AV:170
ucht_end_1
AV:171
uchtstrt_1
BV:2605
use_linkage_1
AV:2901
user_analog_1_1
AV:2909
user_analog_10_1
AV:2910
user_analog_11_1