Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 79

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
EC.EN
Economizer Installed?
EC2.E
Econ.Act.2 Installed?
EC.MN
Economizer Min.Position
EC.MX
Economizer Max.Position
E.TRM
Economzr Trim For SumZ?
E.SEL
Econ ChangeOver Select
DDB.C
Diff Dry Bulb RAT Offset
OA.E.C
OA Enthalpy ChgOvr Selct
OA.EN
Outdr.Enth Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dewpoint Temp Limit
ORH.S
Outside Air RH Sensor
CFM.C
OUTDOOR AIR CFM CONTROL
OCF.S
Outdoor Air CFM Sensor
O.C.MX
Economizer Min.Flow
O.C.MN
IAQ Demand Vent Min.Flow
O.C.DB
Econ.Min.Flow Deadband
E.CFG
ECON.OPERATION CONFIGS
E.P.GN
Economizer Prop.Gain
E.RNG
Economizer Range Adjust
E.SPD
Economizer Speed Adjust
E.DBD
Economizer Deadband
UEFC
UNOCC.ECON.FREE COOLING
FC.CF
Unoc Econ Free Cool Cfg
FC.TM
Unoc Econ Free Cool Time
FC.L.O
Un.Ec.Free Cool OAT Lock
ACT.C
ECON.ACTUATOR CONFIGS
SN.1.1
Econ Serial Number 1
SN.1.2
Econ Serial Number 2
SN.1.3
Econ Serial Number 3
SN.1.4
Econ Serial Number 4
C.A.L1
Econ Ctrl Angle Lo Limit
SN.2.1
Econ 2 Serial Number 1
SN.2.2
Econ 2 Serial Number 2
SN.2.3
Econ 2 Serial Number 3
SN.2.4
Econ 2 Serial Number 4
C.A.L2
Econ 2 Ctrl Angle Lo Limit
T.24.C
TITLE 24 CONFIGS
LOG.F
Log Title 24 Faults
EC.MD
T24 Econ Move Detect
EC.ST
T24 Econ Move SAT Test
S.CHG
T24 Econ Move SAT Change
E.SOD
T24 Econ RAT-OAT Diff
E.CHD
T24 Heat/Cool End Delay
SAT.T
SAT Settling Time
ET.MN
T24 Test Minimum Pos.
ET.MX
T24 Test Maximum Pos.
AC.EC
Economizer Deadband Temp
E.GAP
Econ Fault Detect Gap
E.TMR
Econ Fault Detect Timer
X.CFM
Excess Air CFM
X.TMR
Excess Air Detect Timer
AC.MR
T24 AutoTest SF Run Time
AC.SP
T24 Auto-Test VFD Speed
AC.OP
T24 Auto-Test Econ % Opn
VF.PC
T24 Auto-Test VFD % Chng
EC.DY
T24 Econ Auto-Test Day
EC.TM
T24 Econ Auto-Test Time
EP.MS
ECON POS AT MIN VFD SPEED
EP.XS
ECON POS AT MAX VFD SPEED
Table 66 — Economizer Configuration Table
EXPANSION
RANGE
UNITS
Yes/No
Yes/No
0 to 100
%
0 to 100
%
Yes/No
0 to 3
0 to 3
dF
1 to 5
18 to 28
–40 to 120
dF
50 to 62
dF
Enable/Disable
Enable/Disable
0 to 20000
CFM
0 to 20000
CFM
200 to 1000
CFM
0.7 to 3.0
0.5 to 5
^F
0.1 to 10
0.1 to 2
^F
0 to 2
0 to 720
min
40 to 70
dF
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
Yes/No
1 to 10
10 to 20
0 to 5
5 to 20
0 to 60
10 to 900
0 to 50
50 to 100
0 to 10
2 to 100
10 to 240
400 to 4000
30 to 240
1 to 10
10 to 50
1 to 100
1 to 20
0=Never, 
1=Monday,
2=Tuesday,
3=Wednesday,
4=Thursday,
5=Friday, 
6=Saturday,
7=Sunday
0 to 23
0 to 100
%
0 to 100
%
79
CCN POINT
DEFAULT
ECON_ENA
Yes
ECON_TWO
No
ECONOMIN
5
ECONOMAX
98
ECONTRIM
Yes
ECON_SEL
0
EC_DDBCO
0
OAEC_SEL
4
OAEN_CFG
24
OAT_LOCK
60
OADEWCFG
55
OARHSENS
Disable
OCFMSENS
Disable
OACFMMAX
2000
OACFMMIN
0
OACFM_DB
400
EC_PGAIN
1
EC_RANGE
2.5
EC_SPEED
0.75
EC_DBAND
0.5
UEFC_CFG
0
UEFCTIME
120
UEFCNTLO
50
ECON_SN1
0
ECON_SN2
0
ECON_SN3
0
ECON_SN4
0
ECONCALM
85
ECN2_SN1
0
ECN2_SN2
0
ECN2_SN3
0
ECN2_SN4
0
ECN2CALM
85
T24LOGFL
No
T24ECMDB
1
T24ECSTS
10
T24SATMD
0.2
T24RATDF
15
T24CHDLY
25
SAT_SET
240
T24TSTMN
15
T24TSTMX
85
AC_EC_DB
4
EC_FLGAP
5
EC_FLTMR
20
EX_ARCFM
800
EX_ARTMR
150
T24ACMRT
2
T24ACSPD
20
T24ACOPN
50
T24VFDPC
10
T24_ECDY
6=Saturday
T24_ECTM
2
EPOSMNFS
5
EPOSMXFS
5