Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 209

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

TABLE
T24_CFG
Economizer Installed?
Econ.Act.2 Installed?
SAT Settling Time
MBB Sensor Heat Relocate
Log Title 24 Faults
T24 Econ Move Detect
T24 Econ Move SAT Test
T24 Econ Move SAT Change
T24 Econ RAT-OAT Diff
T24 Heat/Cool End Delay
T24 Test Minimum Pos.
T24 Test Maximum Pos.
Economizer Deadband Temp
Econ Fault Detect Gap
Econ Fault Detect Timer
Excess Air CFM
Excess Air Detect Timer
T24 Econ Auto-Test Day
T24 Econ Auto-Test Time
T24 AutoTest SF Run Time
T24 Auto-Test VFD Speed
T24 Auto-Test Econ % Opn
T24 Auto-Test VFD % Chng
TRIM
Air Temp Lvg SF Trim
RAT Trim
OAT Trim
SPT Trim
Limit Switch Trim
Air Temp Lvg Evap Trim
A1 Discharge Temp Trim
Suction Gas Temp A Trim
Suct.Press.Circ.A Trim
Suct.Press.Circ.B Trim
Dis.Press.Circ.A Trim
Dis.Press.Circ.B Trim
Static Press. Trim (ma)
Bldg. Pressure Trim (ma)
Outside Air CFM Trim (ma)
Supply Air CFM Trim (ma)
Return Air CFM (ma)
UNIT
Machine Control Type
Unit Size (30 to 100)
Fan Mode (0=auto, 1=cont)
Remote Switch Config
CEM Module Installed
Temp.Cmp.Strt.Cool Factr
Temp.Cmp.Strt.Heat Factr
Fan fail shuts down unit
Fan Stat Monitoring Type
VAV Unocc.Fan Retry time
50 Hertz Unit?
MAT Calc Config Type
Reset MAT Table Entries?
MAT Outside Air Default
Altitude........in feet:
MAT Outside Air Default
Startup Delay Time
Auxiliary Relay Config
Space Temp Sensor
Space Temp Offset Sensor
Space Temp Offset Range
Space Air RH Sensor
Return Air RH Sensor
Filter Stat.Sw.Enabled?
Disable T183 Alert
SAV Optimized for Dehumidification
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
DISPLAY NAME
RANGE
UNITS
Yes/No
Yes/No
secs
Yes/No
Yes/No
%
%
deltaF
deltaF
mins
%
%
dF
%
secs
CFM
secs
mins
%
%
%
–10 to 10
^F
–10 to 10
^F
–10 to 10
^F
–10 to 10
^F
–10 to 10
^F
–10 to 10
^F
–10 to 10
^F
–10 to 10
^F
–50 to 50
–50 to 50
–50 to 50
–50 to 50
–2 to 2
–2 to 2
–2 to 2
–2 to 2
–2 to 2
1 to 6
30 to 100
0 to 1
0 to 3
Yes/No
0 to 60
min
0 to 60
min
Yes/No
0 to 2
0 to 720
min
Yes/No
0 to 2
Yes/No
0 to 100
%
0 to 60000
%
0 to 900
secs
0 to 3 (multi-text strings)
Enable/Disable
Enable/Disable
1 to 10
Enable/Disable
Enable/Disable
Enable/Disable
0 to 1
Yes/No
209
POINT NAME
DEFAULT
ECON_ENA
Yes
ECON_TWO
No
SAT_SET
240
HTLATMON
No
T24LOGFL
No
T24ECMDB
1
T24ECSTS
10
T24SATMD
0.2
T24RATDF
15
T24CHDLY
25
T24TSTMN
15
T24TSTMX
85
AC_EC_DB
5
EC_FLGAP
5
EC_FLTMR
20
EX_ARCFM
150
EX_ARTMR
800
T24_ECDY
0
T24_ECTM
2
T24ACMRT
2
T24ACSPD
20
T24ACOPN
50
T24VFDPC
10
SAT_TRIM
0
RAT_TRIM
0
OAT_TRIM
0
SPT_TRIM
0
LSW_TRIM
0
CCT_TRIM
0
DTA1TRIM
RGTATRIM
SPA_TRIM
0
SPB_TRIM
0
DPA_TRIM
0
DPB_TRIM
0
SPMATRIM
0
BPMATRIM
0
OAMATRIM
0
SAMATRIM
0
RAMATRIM
0
CTRLTYPE
4
UNITSIZE
30
FAN_MODE
1
RMTINCFG
0
CEM_BRD
No
TCSTCOOL
0
TCSTHEAT
0
SFS_SHUT
No
SFS_MON
0
SAMPMINS
50
UNIT_HZ
No
MAT_SEL
1
MATRESET
No
MATOAPOS
20
ALTITUDE
0
MATOAPOS
DELAY
0
AUXRELAY
0
SPTSENS
Disable
SPTOSENS
Disable
SPTO_RNG
5
SPRHSENS
Disable
RARHSENS
Disable
FLTS_ENA
Disable
T183DSIA
SAVDEHUM