Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 269

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

APPENDIX I — OPTIONAL GREENSPEED/LOW AMBIENT CONTROL (CONT)
Table BF — ACS320 VFD Low Ambient Parameters Tables, Part 2
ABB ACS320 VFD
LOOKUP VARIABLE
Parameter ID:
PKG
Motor Part Number
VFD Part Number
Drive HP
Number of Motors
LANGUAGE
9901
APPLIC MACRO
9902
MOTOR CTRL MODE
9904
VOLTAGE
9905
N. AMPS
9906
MOTOR NOM FREQ
9907
N. rpm
9908
N. HP
9909
EXT1 COMMANDS
1001
DIRECTION
1003
REF1 SELECT
1103
CONST SPEED SEL
1201
CONST SPEED 7
1208
RELAY OUT 1
1401
RELAY OUTPUT2
1402
RELAY OUT 3
1403
RUN ENABLE
1601
FAULT RESET SEL
1604
START ENABLE 1
1608
Parameter View
1611
MAX AMPS
2003
MIN FREQ
2007
MAX FREQ
2008
SWITCH FREQ
2606
START FCN
2101
STOP FCN
2102
ACCEL/DECEL
2201
ACCEL
2202
DECEL
2203
IR COMP VOLT
2603
COMM FAULT FUNC
3018
COMM FAULT TIME
3019
COMM PROT SEL
9802
TRIAL TIME
3102
DELAY TIME
3103
AR OVERCURRENT
3104
EFB PROTOCOL ID
5301
EFB STATION ID
5302
EFB BAUD RATE
5303
EFB PARITY
5304
EFB CTRL PROFILE
5305
50ZZ000593-DATA 50ZZ000594-DATA 50ZZ000595-DATA 50ZZ000597-DATA 50ZZ000598-DATA 50ZZ000599-DATA
50ZZ000593
50ZZ000594
HD52AK002
HD52AK002
HK30WA524
HK30WA532
7.5
7.5
3
3
English (0)
English (0)
HVAC (1)
HVAC (1)
230
460
19.2
9.9
60Hz
60Hz
1140
1140
7.5
7.5
COMM (10)
COMM (10)
Forward (1)
Forward (1)
COMM (8)
COMM (8)
NOT SEL
NOT SEL
0 Hz
0 Hz
FLT/ALARM (16)
FLT/ALARM (16)
0
0
COMM (8)
COMM (8)
DI4 (4)
DI4 (4)
3
3
33.6
17.3
0Hz
0Hz
60Hz
60Hz
4kHz
4kHz
Auto
Auto
(1) Coast
(1) Coast
Not Sel
Not Sel
10s
10s
10s
10s
0
0
CONST SP 7 (2)
CONST SP 7 (2)
10 s
10 s
LEN(6)
LEN(6)
300.0s
300.0s
6.0s
6.0s
(1) Enable
(1) Enable
0606 hex
0606 hex
43/44
43/44
38.4 kb/s
38.4 kb/s
8 NONE 1
8 NONE 1
DCU PROFILE
DCU PROFILE
50ZZ000595
50ZZ000597
HD52GE382
HD52AK002
HK30WA533
HK30WA525
10
10
3
4
English (0)
English (0)
HVAC (1)
HVAC (1)
380
230
13.2
25.6
60Hz
60Hz
1140
1140
7.5
10
COMM (10)
COMM (10)
Forward (1)
Forward (1)
COMM (8)
COMM (8)
NOT SEL
NOT SEL
0 Hz
0 Hz
FLT/ALARM (16)
FLT/ALARM (16)
0
0
COMM (8)
COMM (8)
DI4 (4)
DI4 (4)
3
3
23.1
44.8
0Hz
0Hz
60Hz
60Hz
4kHz
4kHz
Auto
Auto
(1) Coast
(1) Coast
Not Sel
Not Sel
10s
10s
10s
10s
0
0
CONST SP 7 (2)
CONST SP 7 (2)
10 s
10 s
LEN(6)
LEN(6)
300.0s
300.0s
6.0s
6.0s
(1) Enable
(1) Enable
0606 hex
0606 hex
43/44
43/44
38.4 kb/s
38.4 kb/s
8 NONE 1
8 NONE 1
DCU PROFILE
DCU PROFILE
269
50ZZ000598
50ZZ000599
HD52AK002
HD52GE382
HK30WA533
HK30WA536
10
15
4
4
English (0)
English (0)
HVAC (1)
HVAC (1)
460
380
13.2
17.6
60Hz
60Hz
1140
1140
10
10
COMM (10)
COMM (10)
Forward (1)
Forward (1)
COMM (8)
COMM (8)
NOT SEL
NOT SEL
0 Hz
0 Hz
FLT/ALARM (16)
FLT/ALARM (16)
0
0
COMM (8)
COMM (8)
DI4 (4)
DI4 (4)
3
3
23.1
30.8
0Hz
0Hz
60Hz
60Hz
4kHz
4kHz
Auto
Auto
(1) Coast
(1) Coast
Not Sel
Not Sel
10s
10s
10s
10s
0
0
CONST SP 7 (2)
CONST SP 7 (2)
10 s
10 s
LEN(6)
LEN(6)
300.0s
300.0s
6.0s
6.0s
(1) Enable
(1) Enable
0606 hex
0606 hex
43/44
43/44
38.4 kb/s
38.4 kb/s
8 NONE 1
8 NONE 1
DCU PROFILE
DCU PROFILE