ITEM
ECON
ECONOMIZER CONFIGURATION
EC.EN
Economizer Installed?
EC2.E
Econ.Act.2 Installed?
EC.MN
Economizer Min.Position
EC.MX
Economizer Max.Position
E.TRM
Economzr Trim For SumZ?
E.SEL
Econ ChangeOver Select
DDB.C
Diff Dry Bulb RAT Offset
OA.E.C
OA Enthalpy ChgOvr Selct
OA.EN
Outdr.Enth Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dewpoint Temp Limit
ORH.S
Outside Air RH Sensor
CFM.C
OUTDOOR AIR CFM CONTROL
CFM.COCF.S
Outdoor Air CFM Sensor
CFM.CO.C.MX
Economizer Min.Flow
CFM.CO.C.MN
IAQ Demand Vent Min.Flow
CFM.CO.C.DB
Econ.Min.Flow Deadband
E.CFG
ECON.OPERATION CONFIGS
E.CFGE.P.GN
Economizer Prop.Gain
E.CFGE.RNG
Economizer Range Adjust
E.CFGE.SPD
Economizer Speed Adjust
E.CFGE.DBD
Economizer Deadband
UEFC
UNOCC.ECON.FREE COOLING
UEFCFC.CF
Unoc Econ Free Cool Cfg
UEFCFC.TM
Unoc Econ Free Cool Time
UEFCFC.L.O
Un.Ec.Free Cool OAT Lock
ACT.C
ECON.ACTUATOR CONFIGS
ACTCSN.1.1
Econ Serial Number 1
ACTCSN.1.2
Econ Serial Number 2
ACTCSN.1.3
Econ Serial Number 3
ACTCSN.1.4
Econ Serial Number 4
ACTCC.A.L1
Econ Ctrl Angle Lo Limit
ACTCSN.2.1
Econ 2 Serial Number 1
ACTCSN.2.2
Econ 2 Serial Number 2
ACTCSN.2.3
Econ 2 Serial Number 3
ACTCSN.2.4
Econ 2 Serial Number 4
ACTCC.A.L2
Ecn2 Ctrl Angle Lo Limit
T.24.C
TITLE 24 CONFIGS
T.24.CLOG.F
Log Title 24 Faults
T.24.CEC.MD
T24 Econ Move Detect
T.24.CEC.ST
T24 Econ Move SAT Test
T.24.CS.CHG
T24 Econ Move SAT Change
T.24.CE.SOD
T24 Econ RAT-OAT Diff
T.24.CE.CHD
T24 Heat/Cool End Delay
T.24.CSAT.T
SAT Settling Time
T.24.CET.MN
T24 Test Minimum Pos.
T.24.CET.MX
T24 Test Maximum Pos.
T.24.CAC.EC
Economizer Deadband Temp
T.24.CE.GAP
Econ Fault Detect Gap
T.24.CE.TMR
Econ Fault Detect Timer
T.24.CX.CFM
Excess Air CFM
T.24.CX.TMR
Excess Air Detect Timer
T.24.CAC.MR
T24 AutoTest SF Run Time
T.24.CAC.SP
T24 Auto-Test VFD Speed
T.24.CAC.OP
T24 Auto-Test Econ % Opn
T.24.CVF.PC
T24 Auto-Test VFD % Chng
T.24.CEC.DY
T24 Econ Auto-Test Day
T.24.CEC.TM
T24 Econ Auto-Test Time
EP.MS
ECON POS AT MIN VFD SPEED
EP.XS
ECON POS AT MAX VFD SPEED 0 to 100
BP
BUILDING PRESS. CONFIGS
BP.CF
Building Press. Config
BP.S
Building Pressure Sensor
BP.R
Bldg. Press. (+/-) Range
BP.SP
Building Pressure Setp.
BP.SO
BP Setpoint Offset
BP.P1
Power Exhaust On Setp.1
BP.P2
Power Exhaust On Setp.2
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table H — MODE — CONFIGURATION (cont)
EXPANSION
Yes/No
Yes/No
0 to 100
0 to 100
Yes/No
0 to 3 (multi-text strings)
0 to 3
1 to 5 (multi-text strings)
18 to 28
–40 to 120
50 to 62
Enable/Disable
Enable/Disable
0 to 20000
0 to 20000
200 to 1000
0.7 to 3.0
0.5 to 5
0.1 to 10
0.1 to 2
0 to 2 (multi-text strings)
0 to 720
40 to 71
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
Yes/No
1 to 10
10 to 20
0 to 5
5 to 20
0 to 60
10 to 900
0 to 50
50 to 100
0 to 10
2 to 100
10 to 240
400 to 4000
30 to 240
1 to 10
10 to 50
1 to 100
1 to 20
0=Never, 
1=Monday, 
2=Tuesday,
3=Wednesday, 
4=Thursday, 
5=Friday, 
6=Saturday, 
7=Sunday
0 to 23
0 to 100
0 to 5 (multi-text strings)
Enable/Disable
0.10 to 0.25
–0.25 to 0.25
0 to 0.5
0 to 100
0 to 100
RANGE
UNITS
ECON_ENA
ECON_TWO
%
ECONOMIN
%
ECONOMAX
ECONTRIM
ECON_SEL
dF
EC_DDBCO
OAEC_SEL
OAEN_CFG
dF
OAT_LOCK
dF
OADEWCFG
OARHSENS
OCFMSENS
CFM
OACFMMAX
CFM
OACFMMIN
CFM
OACFM_DB
EC_PGAIN
^F
EC_RANGE
EC_SPEED
^F
EC_DBAND
UEFC_CFG
min
UEFCTIME
dF
UEFCNTLO
ECON_SN1
ECON_SN2
ECON_SN3
ECON_SN4
ECONCALM
ECN2_SN1
ECN2_SN2
ECN2_SN3
ECN2_SN4
ECN2CALM
T24LOGFL
T24ECMDB
T24ECSTS
T24SATMD
T24RATDF
T24CHDLY
SAT_SET
T24TSTMN
T24TSTMX
AC_EC_DB
EC_FLGAP
EC_FLTMR
EX_ARCFM
EX_ARTMR
T24ACMRT
T24ACSPD
T24ACOPN
T24VFDPC
T24_ECDY
T24_ECTM
%
EPOSMNFS
%
EPOSMXFS
BLDG_CFG
BPSENS
"H2O
BP_RANGE
"H2O
BPSP
"H2O
BPSO
%
PES1
%
PES2
194
CCN POINT
DEFAULT
Yes
36, 78, 79
No
36, 78, 79
5
36, 78, 79
98
36, 78, 79
Yes
36, 78, 79
0
36, 79
0
76, 79
4
36, 79, 80
24
36, 79, 80
60
36, 79
55
36, 79, 81
Disable
36, 47, 79
Disable
36, 47, 82
2000
36, 79, 82
0
36, 82
400
36, 79, 82
1
79
2.5
79
0.75
79
0.5
79
0
79, 81
120
79, 82
50
79, 82
0
79
0
79
0
79
0
79
85
79
0
79
0
79
0
79
0
79
85
79
No
77, 79
1
77, 79
10
77, 79
0.2
77, 79
15
77, 79
25
77, 79
240
77, 79
15
77, 79
85
78, 79
4
78, 79
5
78, 79
20
78, 79
800
78, 79
150
78, 79
2
78, 79
20
78, 79
50
78, 79
10
78, 79
6=Saturday 79
2
79
5
5
0
36-37, 83-87
Disable
83
0.25
83
0.05
36, 83
0.05
36, 83
25
36, 83
75
36, 83
PAGE NO.