Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 206

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

TABLE
DEHU
Dehumidification Config
Dehumidification Sensor
Econ disable in DH mode?
Vent Reheat Setpt Select
Vent Reheat RAT offset
Vent Reheat Setpoint
Dehumidify Cool Setpoint
Dehumidify RH Setpoint
Humidimizer Adjust Rate
Humidimizer Prop. Gain
Bypass EXV Max Open
Condenser EXV Max Open
LAT Sample Buffer Length
LAT Sample Rate seconds
DISP
Metric Display
Language Selection
Password Enable
Service Password
Contrast Adjustment
Brightness Adjustment
DLVT
Dmd Level
Lo Heat On
Dmd Level(+) Hi Heat On
Dmd Level(-) Lo Heat Off
Dmd Level
Lo Cool On
Dmd Level(+) Hi Cool On
Dmd Level(-) Lo Cool Off
Cool Trend Demand Level
Heat Trend Demand Level
Cool Trend Time
Heat Trend Time
DMDL
Demand Limit Select
Demand Limit at 20 ma
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Sw.1 Setpt.
Demand Limit Sw.2 Setpt.
ECON
Economizer Installed?
Econ. Act.2 Installed?
Economizer Min.Position
Economizer Max.Position
Economzr trim for sumZ?
Econ ChangeOver Select
OA Enthalpy ChgOvr Selct
Outdr.Enth Compare Value
High OAT Lockout Temp
OA Dewpoint Temp Limit
Outside Air RH Sensor
Outdoor Air CFM Sensor
Economizer Min.Flow
IAQ Demand Vent Min.Flow
Econ.Min.Flow Deadband
Economizer Prop.Gain
Economizer Range Adjust
Economizer Speed Adjust
Economizer Deadband
Unoc Econ Free Cool Cfg
Unoc Econ Free Cool Time
Un.Ec.Free Cool OAT Lock
Econ Serial Number 1
Econ Serial Number 2
Econ Serial Number 3
Econ Serial Number 4
Econ Ctrl Angle Lo Limit
Econ 2 Serial Number 1
Econ 2 Serial Number 2
Econ 2 Serial Number 3
Econ 2 Serial Number 4
Ecn2 Ctrl Angle Lo Limit
ECON POS AT MIN VFD SPEED
ECON POS AT MAX VFD SPEED
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
DISPLAY NAME
RANGE
UNITS
0 to 3
1 to 3
Yes/No
0 to 1
0 to 8
^F
55 to 95
dF
40 to 55
dF
10 to 90
%
secs
%
%
secs
Off/On
0 to 1
Enable/Disable
0000 to 9999
0 to 255
0 to 255
–1 to 2
^F
0.5 to 20.0
^F
0.5 to 2.0
^F
–1 to 2
^F
0.5 to 20.0
^F
0.5 to 2.0
^F
0.1 to 5.0
^F
0.1 to 5.0
^F
30 to 600
sec
30 to 600
sec
0 to 3
0 to 100
%
0 to 99
0 to 60
%
0 to 120
min
0 to 100
%
0 to 100
%
Yes/No
Yes/No
0 to 100
%
0 to 100
%
Yes/No
0 to 3
1 to 5
18 to 28
BTU/LBM
55 to 120
dF
50 to 62
dF
Enable/Disable
Enable/Disable
0 to 20000
CFM
0 to 20000
CFM
200 to 1000
CFM
0.7 to 3.0
0.5 to 5
^F
0.1 to 10
0.1 to 2
^F
0 to 2
0 to 720
min
40 to 70
dF
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 9999
0 to 6
0 to 9999
0 to 254
0 to 90
0 to 100
%
0 to 100
%
206
POINT NAME
DEFAULT
DHSELECT
0
DHSENSOR
1
DHECONEN
No
DHVHTCFG
0
DHVRAOFF
0
DHVHT_SP
70
DHCOOLSP
45
DHRELHSP
55
HMZRRATE
HMZR_PG
BYP_MAX
COND_MAX
LAT_SAMP
LAT_RATE
DISPUNIT
Off
LANGUAGE
0
PASS_EBL
Enable
PASSWORD
1111
CNTR_ADJ
0
BRTS_ADJ
0
DMDLHON
1.5
DMDHHON
0.5
DMDLHOFF
1
DMDLCON
1.5
DMDHCON
0.5
DMDLCOFF
1
CTRENDLV
0.1
HTRENDLV
0.1
CTRENDTM
120
HTRENDTM
120
DMD_CTRL
0
DMT20MA
100
SHED_NUM
0
SHED_DEL
0
SHED_TIM
60
DLSWSP1
80
DLSWSP2
50
ECON_ENA
Yes
ECON_TWO
No
ECONOMIN
5
ECONOMAX
98
ECONTRIM
Yes
ECON_SEL
0
OAEC_SEL
4
OAEN_CFG
24
OAT_LOCK
60
OADEWCFG
55
OARHSENS
Disable
OCFMSENS
Disable
OACFMMAX
2000
OACFMMIN
0
OACFM_DB
400
EC_PGAIN
1
EC_RANGE
2.5
EC_SPEED
0.75
EC_DBAND
0.5
UEFC_CFG
0
UEFCTIME
120
UEFCNTLO
50
ECON_SN1
ECON_SN2
ECON_SN3
ECON_SN4
ECONCALM
85
ECN2_SN1
ECN2_SN2
ECN2_SN3
ECN2_SN4
ECN2CALM
85
EPOSMNFS
5
EPOSMXFS
5

Advertisement