Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 191

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
FANS
FANS
S.FAN
Supply Fan Relay
S.VFD
Supply Fan VFD Speed
E.VFD
Exhaust Fan VFD Speed
P.E.1
Power Exhaust Relay 1
P.E.2
Power Exhaust Relay 2
CDF.1
Condenser Fan Output 1
CDF.2
Condenser Fan Output 2
CDF.3
Condenser Fan Output 3
CDF.4
Condenser Fan Output 4
OV.A
Outdoor Fan VFD A Control Cmd %
OV.B
Outdoor Fan VFD B Control Cmd %
OVA.SPD
ODF_VFD-A Actual Speed %
OVB.SPD
ODF_VFD-B Actual Speed %
COOL
COOLING
A1
Compressor A1 Relay
A2
Compressor A2 Relay
A3
Compressor A3 Relay
B1
Compressor B1 Relay
B2
Compressor B2Relay
B3
Compressor B3 Relay
A1.CP
Compressor A1 Capacity
MLV
Minimum Load Valve Relay
RHV
Humidimizer 3-Way Valve
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
O.A.SP
Outdoor Fan VFD SetPoint A
O.B.SP
Outdoor Fan VFD SetPoint B
HEAT
HEATING
HT.1
Heat Relay 1
H1.CP
Modulating Heat Capacity
HT.2
Heat Relay 2
HT.3
Relay 3 W1 Gas Valve 2
HT.4
Relay 4 W2 Gas Valve 2
HT.5
Relay 5 W1 Gas Valve 3
HT.6
Relay 6 W2 Gas Valve 3
H.I.R
Heat Interlock Relay
HTC.P
Ht.Coil Act.Current Pos.
ACTU
ACTUATORS
ECN.P
Economizer Act.Curr.Pos.
EC2.P
Economzr 2 Act.Curr.Pos.
ECN.C
Economizer Act.Cmd.Pos.
BP1.P
BP 1 Actuator Curr.Pos.
BP1.C
BP 1 Command Position
BP2.P
BP 2 Actuator Curr.Pos.
BP2.C
BP 2 Command Position
HTC.P
Ht.Coil Act.Current Pos.
HTC.C
Ht.Coil Command Position
HMD.P
Humidifier Act.Curr.Pos.
HMD.C
Humidifier Command Pos.
GEN.O
GENERAL OUTPUTS
HUM.R
Humidifier Relay
ALRM
Remote Alarm / Aux Relay
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table G — MODE — INPUTS
EXPANSION
RANGE
UNITS
ON/OFF
SFAN
0 to 100
%
SFAN_VFD
0 to 100
%
EFAN_VFD
ON/OFF
PE1
ON/OFF
PE2
ON/OFF
CONDFAN1
ON/OFF
CONDFAN2
ON/OFF
CONDFAN3
ON/OFF
CONDFAN4
0 to 100
%
OV_A_TST
0 to 100
%
OV_B_TST
0 to 100
%
OVA_SPD
0 to 100
%
OVB_SPD
ON/OFF
CMPA1
ON/OFF
CMPA2
ON/OFF
CMPA3
ON/OFF
CMPB1
ON/OFF
CMPB2
ON/OFF
CMPB3
0 to 100
%
CMPA1CAP
ON/OFF
MLV
ON/OFF
HUM3WVAL
0 to 100
%
COND_EXV
0 to 100
%
BYP_EXV
50 to 140
dF
OV_A_SP
50 to 140
dF
OV_B_SP
ON/OFF
HS1
0 to 100
%
HTMG_CAP
ON/OFF
HS2
ON/OFF
HS3
ON/OFF
HS4
ON/OFF
HS5
ON/OFF
HS6
ON/OFF
HIR
0 to 100
%
HTCLRPOS
0 to 100
%
ECONRPOS
0 to 100
%
ECON2POS
0 to 100
%
ECONOCMD
0 to 100
%
BP1_RPOS
0 to 100
%
BP1_CPOS
0 to 100
%
BP2_RPOS
0 to 100
%
BP2_CPOS
0 to 100
%
HTCLRPOS
0 to 100
%
HTCLCPOS
0 to 100
%
HUMDRPOS
0 to 100
%
HUMDCPOS
ON/OFF
HUMIDRLY
ON/OFF
ALRM
191
CCN POINT
WRITE STATUS
forcible
forcible
forcible