Appendix C - Unit Staging Tables - Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

Table R — Adaptive CV Staging Sequence
(Sizes 030,035)
STAGE
0
COMP
A1
OFF
B1
OFF
OFF
UNIT
030
0%
36%
035
0%
38%
NOTE(S):
a. Minimum load valve.
Table S — VAV (with Digital Compressor) Staging
Sequence (Sizes 030,035)
STAGE
0
COMP
A1
a
OFF
B1
OFF
UNIT
030
0%
035
0%
NOTE(S):
a. On units with optional digital scroll compressor, compressor A1 modulates from
minimum to maximum capacity to provide increased stages.
Table T — VAV and Adaptive CV Staging Sequence
with Minimum Load Valve (Size 040)
STAGE
0
1
a
COMP
A1
OFF
ON
B1
OFF
OFF
B2
OFF
OFF
UNIT
040
0%
36%
NOTE(S):
a. Minimum load valve.
Table X — VAV (with Digital Compressor) Staging Sequence (Sizes 050-075)
STAGE
COMP
A1
a
OFF
A2
OFF
B1
OFF
B2
OFF
UNIT
050
055
060
070
075
NOTE(S):
a. On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.
APPENDIX C — UNIT STAGING TABLES
SEQUENCE
1
a
1
Compressor Status
ON
ON
OFF
Capacity 48/50P
50%
100%
50%
100%
SEQUENCE
1
2
Compressor Status
ON
ON
OFF
ON
Capacity 48/50P
25% to 50%
75% to 100%
25% to 50%
75% to 100%
SEQUENCE
1
2
Compressor Status
ON
ON
OFF
ON
OFF
OFF
Capacity 48/50P
47%
73%
0
1
ON
OFF
OFF
OFF
0%
12% to 23%
0%
13% to 25%
0%
13% to 25%
0%
11% to 23%
0%
13% to 25%
Table U — VAV Digital Compressor Staging
STAGE
2
COMP
ON
A1
a
ON
B1
B2
UNIT
040
NOTE(S):
a. On units with optional digital scroll compressor, compressor A1 modulates from
minimum to maximum capacity to provide increased stages.
Table V — VAV and Adaptive CV Staging Sequence
STAGE
COMP
A1
OFF
B1
OFF
B2
OFF
UNIT
040
0%
Table W — VAV and Adaptive Cv Staging
STAGE
COMP
A1
3
A2
B1
ON
B2
ON
UNIT
ON
050
055
100%
060
070
075
NOTE(S):
a. Minimum load valve.
SEQUENCE
2
Compressor Status
ON
OFF
ON
OFF
Capacity 48/50P
38% to 50%
38% to 50%
38% to 50%
34% to 46%
38% to 50%
219
Sequence (Size 040)
SEQUENCE
0
1
Compressor Status
OFF
ON
OFF
OFF
OFF
OFF
Capacity 48/50P
0%
23% to 47%
50% to 73%
without Minimum Load Valve
(Size 040)
SEQUENCE
0
1
2
Compressor Status
OFF
ON
ON
OFF
OFF
OFF
Capacity 48/50P
27%
47%
Sequence (Sizes 050-075)
SEQUENCE
0
1
a
1
2
Compressor Status
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
Capacity 48/50P
0%
15%
23%
50%
0%
17%
25%
50%
0%
18%
25%
50%
0%
16%
23%
46%
0%
19%
25%
50%
3
ON
ON
ON
OFF
62% to 73%
63% to 75%
63% to 75%
61% to 73%
63% to 75%
2
3
ON
ON
ON
ON
OFF
ON
77% to 100%
3
4
ON
ON
ON
ON
OFF
ON
73%
100%
3
4
ON
ON
ON
ON
ON
ON
OFF
ON
73%
100%
75%
100%
75%
100%
73%
100%
75%
100%
4
ON
ON
ON
ON
88% to 100%
88% to 100%
88% to 100%
89% to 100%
88% to 100%