Set Clock On Vfd (If Installed); Programming Operating Schedules - Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

Configuration
BP
BP.CF=5 (Return/Exhaust — Fan
Tracking Control)

Under Configuration
BP, the following configuration may be
adjusted:
BP.SP
Building Pressure Setpt. (see note below)
Under Configuration
BP
may be adjusted:
BP.FS
VFD/Act. Fire Speed
BP.MN
VFD/Act. Min. Speed
BP.MX
VFD Maximum Speed
Under Configuration
BP
tions may be adjusted:
FT.CF
Fan Track Learn Enable (Not recommended
without system air balance validation. See note.)
FT.TM
Fan Track Learn Rate (See note below; not used
when Fan Track Learning is disabled.)
FT.ST
Fan Track Initial DCFM
FT.MX Fan Track Max Clamp (See note below; not used
when Fan Track Learning is disabled.)
FT.MN Fan Track Minimum Clamp (See note below; not
used when Fan Track Learning is disabled.)
FT.AD
Fan Track Max Correction (See note below; not
used when Fan Track Learning is disabled.)
FT.OF
Fan Track Internl EEPROM (See note below;
not used when Fan Track Learning is disabled.)
FT.RM Fan Track Internal RAM (See note below; not
used when Fan Track Learning is disabled.)
FT.RS
Fan Track Reset Internal (See note below; not
used when Fan Track Learning is disabled.)
SCF.C
Supply Air CFM Config (See note below; not
used when Fan Track Learning is disabled.)
NOTE: These configurations are used only if Fan Track Learning
is enabled. When Fan Track Learning is enabled, the control will
add an offset to the Fan Track Initial DCFM (Configuration
BP
FAN.T
FT.ST) if the building pressure deviates from the
Building Pressure Set Point (BP.SP). Periodically, at the rate set
by the Fan Track Learn Rate (FT.TM), the delta cfm is adjusted
upward or downward with a maximum adjustment at a given in-
stance to be no greater than Fan Track Max correction (FT.AD).
The delta cfm cannot ever be adjusted to be greater than or less
than the Fan Track Max Clamp (FT.MX) or less than the Fan
Track Minimum Clamp (FT.MN). Fan track learning will not
work properly unless the air balancer has determined the FN.MX
and FN.MN for the building. A single delta as determined via a
system air balance should be adequate; otherwise, select one of
the direct BP controls.

Set Clock on VFD (If Installed)

ACH550/ACS320 PROCEDURE
The clock set mode is used for setting the date and time for the in-
ternal clock of the VFD. In order to use the timer functions of the
VFD control, the internal clock must be set. The date is used to de-
termine weekdays and is visible in the fault logs. Refer to the VFD
section in Appendix D on page 221 for information on operating
the VFD and using the keypad.
To set the clock, perform the following procedure from the VFD
keypad:
1.
Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2.
Use UP or DOWN keys to highlight TIME AND DATE
SET on display screen and press ENTER (SOFT KEY 2).
The clock set parameter list will be displayed.
B.V.A, the following configurations
FAN.T, the following configura-
3.
Use UP or DOWN keys to highlight CLOCK VISIBILITY
and press SEL (SOFT KEY 2). This parameter is used to dis-
play or hide the clock on the screen. Use UP or DOWN keys
to change the parameter setting. Press OK (SOFT KEY 2) to
save the configuration and return to the Clock Set menu.
4.
Use UP or DOWN keys to highlight SET TIME and press
SEL (SOFT KEY 2). Use UP or DOWN keys to change
the hours and minutes. Press OK (SOFT KEY 2) to save
the configuration and return to the Clock Set menu.
5.
Use UP or DOWN keys to highlight TIME FORMAT and
press SEL (SOFT KEY 2). Use UP or DOWN keys to
change the parameter setting. Press OK (SOFT KEY 2) to
save the configuration and return to the Clock Set menu.
6.
Use UP or DOWN keys to highlight SET DATE and press
SEL (SOFT KEY 2). Use UP or DOWN keys to change
the day, month, and year. Press OK (SOFT KEY 2) to save
the configuration and return to the Clock Set menu.
7.
Use UP or DOWN keys to highlight DATE FORMAT and
press SEL (SOFT KEY 2). Use UP or DOWN keys to
change the parameter setting. Press OK (SOFT KEY 2) to
save the configuration and return to the Clock Set menu.
8.
Press EXIT (SOFT KEY 1) twice to return to the main menu.
ACH580 PROCEDURE
Use the clock set mode to set the date and time for the internal
clock of the VFD. In order to use the timer functions of the VFD
control, the internal clock must be set. The date is used to deter-
mine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1.
Select MENU (press
2.
Use the UP or DOWN keys to highlight PRIMARY SETT.
on the display screen and press ENTER (press
Sub list will be displayed.
3.
Use the UP or DOWN keys to highlight clock, region, and
display, then press SEL (press
to display or hide the clock on the screen. Use the UP or
DOWN keys to change the parameter setting. Press OK
(press
) to save the configuration and return to the Sub
list menu.
 
4.
Use the UP or DOWN keys to highlight SET TIME and press
SEL (press
hours and minutes. Press OK (press
uration and return to the Clock Set menu.
5.
Use the UP or DOWN keys to highlight TIME FORMAT and
press SEL (press
change the parameter setting. Press OK (press
the configuration and return to the Clock Set menu.
6.
Use the UP or DOWN keys to highlight SET DATE and
press SEL (press
change the day, month, and year. Press OK (press
save the configuration and return to the Clock Set menu.
7.
Use the UP or DOWN keys to highlight DATE FORMAT
and press SEL (press
change the parameter setting. Press OK (press
the configuration and return to the Clock Set menu.
8.
Press BACK (press

Programming Operating Schedules

The ComfortLink controls will accommodate up to eight different
schedules (Periods 1 through 8), and each schedule is assigned to
the desired days of the week. Each schedule includes an occupied
on and off time. For example, to set an occupied schedule for
8 AM to 5 PM for Monday through Friday, set days Monday
through Friday to ON for Period 1. Then configure the Period 1
Occupied From point to 08:00 and the Period 1 Occupied To point
to 17:00. To create a different weekend schedule, use Period 2 and
set days Saturday and Sunday to ON with the desired Occupied
On and Off times.
37
). The Main menu will display.
). This parameter is used
). Use the UP or DOWN keys to change the
) to save the config-
). Use the UP or DOWN keys to
). Use the UP or DOWN keys to
). Use the UP or DOWN keys to
) twice to return to the main menu.
). The
) to save
) to
) to save