Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 189

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
HEAT
TEST HEATING
HT.ST
Requested Heat Stage
HT.1
Heat Relay 1
H1.CP
Modulating Heat Capacity
HT.2
Heat Relay 2
HT.3
Relay 3 W1 Gas Valve 2
HT.4
Relay 4 W2 Gas Valve 2
HT.5
Relay 5 W1 Gas Valve 3
HT.6
Relay 6 W2 Gas Valve 3
H.I.R
Heat Interlock Relay
HTC.C
Ht.Coil Command Position
ITEM
AIR.T
AIR TEMPERATURES
CTRL
CONTROL TEMPS
CTRLEDT
Evaporator Discharge Tmp
CTRLLAT
Leaving Air Temperature
CTRLMAT
Mixed Air Temperature
CTRLR.TMP
Controlling Return Temp
CTRLS.TMP
Controlling Space Temp
SAT
Air Tmp Lvg Supply Fan
OAT
Outside Air Temperature
RAT
Return Air Temperature
SPT
Space Temperature
SPTO
Space Temperature Offset
CCT
Air Temp Lvg Evap Coil
S.G.LS
Staged Heat LAT Sum
S.G.L1
Staged Heat LAT 1
S.G.L2
Staged Heat LAT 2
S.G.L3
Staged Heat LAT 3
S.G.LM
Staged Gas Limit Sw.Temp
REF.T
REFRIGERANT TEMPERATURES
SCT.A
Cir A Sat.Condensing Tmp
SST.A
Cir A Sat.Suction Temp.
SCT.B
Cir B Sat.Condensing Tmp
SST.B
Cir B Sat.Suction Temp.
RGT.A
Suction Gas Temp Circ A
DT.A1
A1 Discharge Temperature
ITEM
AIR.P
AIR PRESSURES
SP
Static Pressure
BP
Building Pressure
BP.NT
Network Building Pressure
REF.P
REFRIGERANT PRESSURES
DP.A
Cir A Discharge Pressure
SP.A
Cir A Suction Pressure
DP.B
Cir B Discharge Pressure
SP.B
Cit B Suction Pressure
ITEM
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
V.C.ON
VAV Occ. Cool On Delta
V.C.OF
VAV Occ. Cool Off Delta
SASP
Supply Air Setpoint
SA.HI
Supply Air Setpoint Hi
SA.LO
Supply Air Setpoint Lo
SA.HT
Heating Supply Air Setpt
T.PRG
Tempering Purge SASP
T.CL
Tempering in Cool SASP
T.V.OC
Tempering Vent Occ SASP
T.V.UN
Tempering Vent Unocc. SASP
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table B — MODE — SERVICE TEST (cont)
EXPANSION
0 to 100
0 to 100
0 to n
ON/OFF
0 to 100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 to 100
Table C — MODE — TEMPERATURES
EXPANSION
Table D — MODE — PRESSURES
EXPANSION
Table E — MODE — SETPOINTS
EXPANSION
RANGE
UNITS
CCN POINT
%
CEXVHTST
%
BEXVHTST
HTST_TST
HS1_TST
%
MGAS_TST
HS2_TST
HS3_TST
HS4_TST
HS5_TST
HS6_TST
HIR_TST
%
HTCLHEAT
RANGE
UNITS
dF
dF
dF
dF
dF
dF
–40 to 240
dF
dF
–40 to 240
dF
^F
dF
dF
dF
dF
dF
dF
dF
dF
dF
dF
dF
dF
RANGE
UNITS
"H2O
"H2O
–2 to 2
"H2O
PSIG
PSIG
PSIG
PSIG
RANGE
UNITS
40 to 99
dF
40 to 99
dF
40 to 99
dF
40 to 110
dF
2 to 10
deltaF
0 to 25
deltaF
1 to 25
deltaF
45 to 75
dF
45 to 75
dF
45 to 75
dF
80 to 120
dF
–20 to 80
dF
5 to 75
dF
–20 to 80
dF
–20 to 80
dF
189
WRITE STATUS
CCN POINT
WRITE STATUS
EDT
LAT
MAT
RETURN_T
forcible
SPACE_T
forcible
SAT
OAT
forcible
RAT
forcible
SPT
forcible
SPTO
forcible
CCT
LAT_SGAS
LAT1SGAS
LAT2SGAS
LAT3SGAS
LIMSWTMP
SCTA
SSTA
SCTB
SSTB
RGTA
DTA1
CCN POINT
WRITE STATUS
SP
BP
BP.NTWRK
DP_A
SP_A
DP_B
SP_B
CCN POINT
OHSP
68
OCSP
75
UHSP
55
UCSP
90
HCSP_GAP
5
VAVOCON
3.5
VAVOCOFF
2
SASP
55
SASP_HI
55
SASP_LO
60
SASPHEAT
85
TEMPPURG
50
TEMPCOOL
5
TEMPVOCC
65
TEMPVUNC
50
PAGE NO.
41
41
41
41
41
41
41
41
41
41
41
41
DEFAULT