Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 235

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

Fig. L — Remove Main Fan
(Frame Sizes R1 up to R3)
Fig. M — Remove Main Fan (Frame Size R4)
Fig. N — Main Fan (Frame Sizes R5 up to R8)
Fig. O — Remove Main Fan
(Frame Sizes R5 up to R8)
APPENDIX D — VFD INFORMATION (CONT)
235
AUXILIARY COOLING FAN REPLACEMENT IP21
and IP55 (UL Type 1 and UL Type 12)
The VFD IP21 and IP55 / UL Type 1 and 12 enclosures have an
additional internal fan to circulate air inside the enclosure.
To replace the internal enclosure fan for frame sizes R6 to R8, per-
form the following (see Fig. P and Q):
1.
Remove power from drive. Wait for 5 minutes and then make
sure by measuring that there is no voltage.
2.
Remove the front cover.
3.
Unplug fan power supply wires from the drive.
4.
Release the retaining clips.
5.
Pull off the fan.
6.
Install the new fan in reverse order.
NOTE: Make sure that the arrow on the fan points up.
To replace the internal enclosure fan for frame sizes IP55
(UL Type 12) R1, R2, and R3, perform the following (see
Fig. R-U):
1.
Remove power from drive (R1, R2, and R3).
2.
Remove the front cover (R1, R2, and R3).
3.
Unplug fan power supply wires from drive (R1, R2, and R3).
4.
Remove the finger-guard by inserting a screwdriver into the
finger-guard hole (R1, R2 only).
5.
Unplug fan power supply wires from drive (R1, R2, and R3).
6.
Pull off the plastic housing (R3 only).
7.
Pull off the fan (R1, R2, and R3).
8.
Install the new fan by following these steps in reverse order
(R1, R2, and R3).
NOTE: Make sure that the arrow on the fan points the same direc-
tion as the arrow on the drive frame.
To replace the internal enclosure fan for frame sizes IP55
(UL Type 12) frame R4; IP21 and IP55 (UL Type 1 and UL
Type 12) frame R5, perform the following (see Fig. R, S, and V):
1.
Remove power from drive.
2.
Remove the front cover.
3.
Unplug fan power supply wires from the drive.
4.
Remove the finger-guard: Insert a screwdriver into the hole of
the finger-guard.
5.
Unplug the fan power supply wires from the drive.
6.
Pull off the plastic housing.
7.
Pull off the fan.
8.
Install the new fan by following these steps in reverse order.
NOTE: Make sure that the arrow on the fan points the same direc-
tion as the arrow on the drive frame.
CONTROL PANEL CLEANING
Use a soft damp cloth to clean the control panel. Avoid harsh
cleaners which could scratch the display window.
BATTERY REPLACEMENT
A battery is only used in assistant control panels that have the
clock function available and enabled. The battery keeps the clock
operating in memory during power interruptions. The expected
life for the battery is greater than ten years. To remove the battery,
use a coin to rotate the battery holder on the back of the control
panel. Replace the battery with CR2032.