Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 188

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
TEST
Service Test Mode
STOP
Local Machine Disable
S.STP
Soft Stop Request
FAN.F
Supply Fan Request
INDP
TEST INDEPENDENT OUTPUTS
HUM.R
Humidifier Relay
ALRM
Remote Alarm / Aux Relay
FANS
TEST FANS
F.MOD
Fan Test Automatic?
E.POS
Econo Damper Command Pos
S.FAN
Supply Fan Relay
S.VFD
Supply Fan VFD Speed
P.E.1
Power Exhaust Relay 1
E.VFD
Exhaust Fan VFD Speed
P.E.2
Power Exhaust Relay 2
BP1.C
BP 1 Command Position
BP2.C
BP 2 Command Position
CDF.1
Condenser Fan Output 1
CDF.2
Condenser Fan Output 2
CDF.3
Condenser Fan Output 3
CDF.4
Condenser Fan Output 4
OV.A
Outdoor Fan VFD A Control Cmd %
OV.B
Outdoor Fan VFD B Control Cmd %
E.TST
ECONOMIZER AUTO-TEST
 EC.TR
Run Economizer Auto-Test
Test Status & Timer
 EC.DT
0=WAITING, 1=00:00:00
 S.VFD
VFD1 Actual Speed
 TORQ
VFD1 Torque Moving Avg.
 ECN.P
Economizer Act.Curr.Pos.
 EC2.P
Economzr 2 Act.Curr.Pos.
Econ Auto-Test Result 
 ET.SR
0=NOT RUN, 1=RUNNING,
2=PASSED,3=FAILED
ACT.C
CALIBRATE TEST-ACTUATORS
ECN.C
Economizer Act.Cmd.Pos.
EC.CL
Economizer Calibrate Cmd
ECN.A
Econ Act. Control Angle
EC2.C
Economzr 2 Act.Cmd.Pos.
E2.CL
Economzr 2 Calibrate Cmd
EC2.A
Econ2 Act. Control Angle
BP1.C
BP 1 Command Position
B1.CL
BP 1 Actuator Cal Cmd
BP1.A
BP Act.1 Control Angle
BP1.M
BP 1 Actuator Max Pos.
BP2.C
BP 2 Command Position
B2.CL
BP 2 Actuator Cal Cmd
BP2.A
BP Act.2 Control Angle
BP2.M
BP 2 Actuator Max Pos.
HTC.C
Ht.Coil Command Position
HT.CL
Heating Coil Act. Cal.Cmd
HTC.A
Heat Coil Act.Ctl.Angle
HMD.C
Humidifier Command Pos.
HM.CL
Humidifier Act. Cal.Cmd
HMD.A
Humidifier Act.Ctrl.Ang.
HMZR
TEST HUMIDIMIZER
RHV
HumidiMiZer 3-way Valve
C.EXV
Condenser EXV Position
B.EXV
Bypass EXV Position
C.CAL
Condenser EXV Calibrate
B.CAL
Bypass EXV Calibrate
COOL
TEST COOLING
E.POS
Econo Damper Command Pos
SP.SP
Static Pressure Setpoint
CL.ST
Requested Cool Stage
MLV
Minimum Load Valve Relay
A1
Compressor A1 Relay
A1.CP
Compressor A1 Capacity
A1.B1
Two Circuit Start A1,B1
A2
Compressor A2 Relay
A3
Compressor A3 Relay
B1
Compressor B1 Relay
B2
Compressor B2 Relay
B3
Compressor B3 Relay
RHV
HumidiMiZer 3-way Valve
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table B — MODE — SERVICE TEST
EXPANSION
ON/OFF
YES/NO
YES/NO
YES/NO
ON/OFF
ON/OFF
YES/NO
ON/OFF
0 to 100
ON/OFF
0 to 100
ON/OFF
0 to 100
0 to 100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 to 100
0 to 100
YES/NO
0 to 100
0 to 100
0 to 100
YES/NO
read only
0 to 100
YES/NO
read only
0 to 100
YES/NO
read only
0 to 100
0 to 100
YES/NO
read only
0 to 100
0 to 100
YES/NO
read only
0 to 100
YES/NO
read only
Off/On
0 to 100
0 to 100
Off/On
Off/On
0 to 100
0 to 5
0 to n
ON/OFF
ON/OFF
20 to 100
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Off/On
RANGE
UNITS
CCN POINT
MAN_CTRL
UNITSTOP
SOFTSTOP
SFANFORC
HUMR_TST
ALRM_TST
FANAUTO
%
ECONFANS
SFAN_TST
%
SFVFDTST
PE1_TST
%
EFVFDTST
PE2_TST
%
BLDPTST1
%
BLDPTST2
CDF1_TST
CDF2_TST
CDF3_TST
CDF4_TST
%
OV_A_TST
%
OV_B_TST
AC_EC
DD_TEXT
VFD1_SPD
%
VFD1TMAV
%
ECONOPOS
ECON2POS
AC_EC_ST
%
ECON1TST
ECONOCAL
ECONCANG
%
ECON2TST
ECON2CAL
ECN2CANG
%
BLDG1TST
BLDG1CAL
BP1_CANG
%
BP1SETMX
%
BLDG2TST
BLDG2CAL
BP2_CANG
%
BP2SETMX
%
HTCLACTC
HCOILCAL
HTCLCANG
%
HUMD_TST
HUMIDCAL
HUMDCANG
RHVH_TST
%
CEXVHTST
%
BEXVHTST
CEXV_CAL
BEXV_CAL
%
ECONCOOL
"H2O
SPSP_TST
CLST_TST
MLV_TST
CMPA1TST
A1CAPTST
CMPABTST
CMPA2TST
CMPA3TST
CMPB1TST
CMPB2TST
CMPB3TST
RHVH_TST
188
WRITE STATUS
PAGE NO.
38
config
38
forcible
38
forcible
38
39
39
38, 39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
76
76
76
76
76
76
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
40, 56
40, 56
40, 56
40
40
41
41
41
39
39
39
39
39
39
39
39
39
41