Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 89

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
DCV.C
DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position
IAQ.M
IAQ Demand Vent Min.Pos.
O.C.MX
Economizer Min.Flow
O.C.MN
IAQ Demand Vent Min.Flow
O.C.DB
Econ.Min.Flow Deadband
AQ.CF
AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config
IQ.A.F
IAQ 4-20 ma Fan Config
IQ.I.C
IAQ Discrete Input Config
IQ.I.F
IAQ Disc.In. Fan Config
OQ.A.C
OAQ 4-20ma Sensor Config
AQ.SP
AIR QUALITY SETPOINTS
IQ.O.P
IAQ Econo Override Pos.
IQ.O.C
IAQ Override Flow
DAQ.L
Diff.Air Quality LoLimit
DAQ.H
Diff. Air Quality HiLimit
D.F.OF
DAQ PPM Fan Off Setpoint
D.F.ON
DAQ PPM Fan On Setpoint
IAQ.R
Diff. AQ Responsiveness
OAQ.L
OAQ Lockout Value
OAQ.U
User Determined OAQ
AQ.S.R
AIR QUALITY SENSOR RANGE
IQ.R.L
IAQ Low Reference
IQ.R.H
IAQ High Reference
OQ.R.L
OAQ Low Reference
OQ.R.H
OAQ High Reference
IAQ.P
IAQ PRE-OCCUPIED PURGE
IQ.PG
IAQ Purge
IQ.P.T
IAQ Purge Duration
IQ.P.L
IAQ Purge LoTemp Min Pos
IQ.P.H
IAQ Purge HiTemp Min Pos
IQ.L.O
IAQ Purge OAT Lockout
IAQ Analog Sensor Config (Configuration
IQ.A.C)
This is used to configure the type of IAQ position control. It has
the following options:
IQ.A.C = 0 (No analog input). If there is no other minimum
position control, the economizer minimum position is Con-
figuration
IAQ
EC.MN and there will be no IAQ control.
IQ.A.C = 1 (IAQ analog input). An indoor air (space or return
air) CO
sensor is installed. If an outdoor air CO
2
also installed, or OAQ is broadcast on the CCN, or if a default
OAQ value is used, then the unit can perform IAQ control.
IQ.A.C = 2 (IAQ analog input with minimum position
override) — If the differential between IAQ and OAQ is
above Configuration
omizer minimum position will be the IAQ override posi-
tion (Configuration
IAQ
IQ.A.C = 3 (4 to 20 mA minimum position) — With a 4 to
20 mA signal connected to TB201 terminal 7 and 8, the
economizer minimum position will be scaled linearly from
0% (4 mA) to EC.MN (20 mA).
IQ.A.C = 4 (10K potentiometer minimum position) — With a
10K linear potentiometer connected to TB201 terminal 7 and
8, the economizer minimum position will be scaled linearly
from 0% (0 ohms) to EC.MN (10,000 ohms).
IAQ Analog Fan Config (Configuration
IQ.A.F)
This configuration is used to configure the control of the indoor
fan. If this option is used, then the IAQ sensor must be in the space
and not in the return duct.
Table 69 — Indoor Air Quality Configuration
EXPANSION
IAQ
AQ.CF
sensor is
2
IAQ
AQ.SP
DAQ.H, the econ-
AQ.SP
IQ.O.P).
IAQ
AQ.CF
RANGE
UNITS
0 to 100
%
0 to 100
%
0 to 20000
CFM
0 to 20000
CFM
200 to 1000
CFM
0 to 4
0 to 2
0 to 2
0 to 2
0 to 2
0 to 100
%
0 to 31000
CFM
0 to 1000
100 to 2000
0 to 2000
0 to 2000
–5 to 5
0 to 2000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
Yes/No
5 to 60
min
0 to 100
%
0 to 100
%
35 to 70
dF

It has the following configurations:
IQ.A.F = 0 (No Fan Start) — IAQ demand will never
override normal indoor fan operation during occupied or
unoccupied period and turn it on.
IQ.A.F = 1 (Fan On If Occupied) — IAQ demand will
override normal indoor fan operation and turn it on (if off)
only during the occupied period (CV operation with auto-
matic fan).
IQ.A.F = 2 (Fan On Occupied/Unoccupied) — IAQ demand
will always override normal indoor fan operation and turn it
on (if off) during both the occupied and unoccupied period.
For IQ.A.F = 1 or 2, the fan will be turned on as described
above when DAQ is above the DAQ Fan On Set Point (Con-
figuration
off when DAQ is below the DAQ Fan Off Set Point (Configu-
ration
IAQ
up to respond to a discrete IAQ input. The discrete input is
connected to TB202 terminal 12 and 13.
IAQ Discrete Input Config (Configuration
IQ.I.C)
This configuration is used to set the type of IAQ sensor. The fol-
lowing are the options:
IQ.I.C = 0 (No Discrete Input) — No discrete input will be
used and the standard IAQ sensor input will be used.
IQ.I.C = 1 (IAQ Discrete Input) — The IAQ level (high or
low) will be indicated by the discrete input. When the IAQ
level is low, the economizer minimum position will be
Configuration
IQ.I.C = 2 (IAQ Discrete Input with Minimum Position
Override) — The IAQ level (high or low) will be indicated by
the discrete input and the economizer minimum position will
be the IAQ override position, IQ.O.P (when high). It is also
89
CCN POINT
ECONOMIN
IAQMINP
OACFMMAX
OACFMMIN
OACFM_DB
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
OAQANCFG
IAQOVPOS
IAQOVCFM
DAQ_LOW
DAQ_HIGH
DAQFNOFF
DAQFNON
IAQREACT
OAQLOCK
OAQ_USER
IAQREFL
IAQREFH
OAQREFL
OAQREFH
IAQPURGE
IAQPTIME
IAQPLTMP
IAQPHTMP
IAQPNTLO
IAQ
AQ.SP
D.F.ON). The fan will be turned
AQ.SP
D.F.OF). The control can also be set

IAQ
DCV.C
IAQ.M.
DEFAULT
5
0
2000
0
400
0
0
0
0
0
100
10000
100
700
200
400
0
0
400
0
2000
0
2000
No
15
10
35
50

IAQ
AQ.CF