Carrier Weathermaster 48P030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 192

Single package large rooftop units with comfortlink version 9.x controls
Table of Contents

Advertisement

ITEM
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
SIZE
Unit Size (30 to 100)
FN.MD
Fan Mode (0=Auto, 1=Cont)
RM.CF
Remote Switch Config
CEM
CEM Module Installed
TCS.C
Temp.Cmp.Strt.Cool Factr
TCS.H
Temp.Cmp.Strt.Heat Factr
SFS.S
Fan Fail Shuts Down Unit
SFS.M
Fan Stat Monitoring Type
VAV.S
VAV Unocc.Fan Retry Time
50.HZ
50 Hertz Unit?
MAT.S
MAT Calc Config
MAT.R
Reset MAT Table Entries?
MAT.D
MAT Outside Air Default
ALTI
Altitude........in feet:
DLAY
Startup Delay Time
AUX.R
Auxiliary Relay Config
D.183
Disable T183 Alert
SAV Optimized for
SV.DH
Dehumidification
SENS
INPUT SENSOR CONFIG
SENSSPT.S
Space Temp Sensor
SENSSP.O.S
Space Temp Offset Sensor
SENSSP.O.R
Space Temp Offset Range
SENSSRH.S
Space Air RH Sensor
SENSRRH.S
Return Air RH Sensor
SENSFLT.S
Filter Stat.Sw.Enabled?
FACT
FACTORY CONFIGURATION
FACTMD.MN
Undefined
FACTF.RST
Perform Factory Restore?
FACTVOLT
UNIT_VOLTAGE
COOL
COOLING CONFIGURATION
A1.EN
Enable Compressor A1
A2.EN
Enable Compressor A2
A3.EN
Enable Compressor A3
B1.EN
Enable Compressor B1
B2.EN
Enable Compressor B2
B3.EN
Enable Compressor B3
CS.A1
CSB A1 Feedback Alarm
CS.A2
CSB A2 Feedback Alarm
CS.A3
CSB A3 Feedback Alarm
CS.B1
CSB B1 Feedback Alarm
CS.B2
CSB B2 Feedback Alarm
CS.B3
CSB B3 Feedback Alarm
Z.GN
Capacity Threshold Adjst
MC.LO
Compressor Lockout Temp
LLAG
Lead/Lag Configuration
M.M.
Motor Master Control?
 SCT.H
Maximum Condenser Temp
OV.EN
Outdoor VFD Enable
ODV.A
OUTDOOR VFD-A CONFIGS
N.VLT
OV-A Nominal Motor Volts
N.AMP
OV-A Nominal Motor Amps
N.FRQ
OV-A Nominal Motor Freq
N.RPM
OV-A Nominal Motor rpm
N.PWR
OV-A Nominal Motor HPwr
OV-A Motor Direction
M.DIR
0=FORWARD, 1=REVERSE
ACCL
OV-A Acceleration Time
DECL
OV-A Deceleration Time
SW.FQ
OV-A Switching Frequency
ODV.B
OUTDOOR VFD-B CONFIGS
N.VLT
OV-B Nominal Motor Volts
N.AMP
OV-B Nominal Motor Amps
N.FRQ
OV-B Nominal Motor Freq
N.RPM
OV-B Nominal Motor rpm
N.PWR
OV-B Nominal Motor HPwr
OV-B Motor Direction
M.DIR
0=FORWARD, 1=REVERSE
ACCL
OV-B Acceleration Time
DECL
OV-B Deceleration Time
SW.FQ
OV-B Switching Frequency
O.PID
OUTDOOR VFD PID CONFIGS
OV.RR
Outdoor VFD PI Run Rate
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
Table H — MODE — CONFIGURATION
EXPANSION
1 to 4 (multi-text strings)
30 to 100
0 to 1 (multi-text strings)
0 to 3 (multi-text strings)
Yes/No
0 to 60
0 to 60
Yes/No
0 to 2 (multi-text strings)
0 to 720
Yes/No
0 to 2 (multi-text strings)
Yes/No
0 to 100
0 to 60000
0 to 900
0 to 3 (multi-text strings)
0 to 1
Yes/No
Enable/Disable
Enable/Disable
1 to 10
Enable/Disable
Enable/Disable
Enable/Disable
0=NO, 1=YES
240 to 575
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
0.1 to 10.0
–25 to 55
0, 1, 2
Yes/No
100 to 150
Yes/No
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
0 to 1
0 to 1800
0 to 1800
0 to 3
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
0 to 1
0 to 1800
0 to 1800
0 to 3
5 to 120
RANGE
UNITS
CTRLTYPE
UNITSIZE
FAN_MODE
RMTINCFG
CEM_BRD
min
TCSTCOOL
min
TCSTHEAT
SFS_SHUT
SFS_MON
min
SAMPMINS
UNIT_HZ
MAT_SEL
MATRESET
%
MATOAPOS
ALTITUDE
secs
DELAY
AUXRELAY
SPTSENS
SPTOSENS
SPTO_RNG
SPRHSENS
RARHSENS
FLTS_ENA
MODEL_NM
FACT_RST
UNITVOLT
CMPA1ENA
CMPA2ENA
CMPA3ENA
CMPB1ENA
CMPB2ENA
CMPB3ENA
CSB_A1EN
CSB_A2EN
CSB_A3EN
CSB_B1EN
CSB_B2EN
CSB_B3EN
Z_GAIN
dF
OATLCOMP
LEAD_LAG
MOTRMAST
dF
SCT_MAX
OV_ENA
v
OVA_NVLT
A
OVA_NAMP
Hz
OVA_NFRQ
rpm
OVA_Nrpm
hp
OVA_NPWR
OVA_MDIR
s
OVA_ACCL
s
OVA_DECL
OVA_SWFQ
v
OVB_NVLT
A
OVB_NAMP
Hz
HOVB_NFRQ 60 35
rpm
OVB_Nrpm 850
hp
OVB_NPWR
OVB_MDIR
OVB_ACCL
OVB_DECL
OVB_SWFQ
OV_RATE
192
CCN POINT
DEFAULT
4
35, 44, 49, 64
30
47, 49
1
35, 47
0
42, 47, 103
No
47
0
47, 96
0
47, 96
No
48, 75
0
48, 74
50
48
No
48, 49
1
48, 57
No
48, 57
20
48
0
48
0
48
0
48
1
48
48
Disable
35, 48
Disable
48, 104
5
48, 104
Disable
47, 48, 91
Disable
47, 48, 91
Disable
48, 75
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
Enable
50
1
50, 55
53
50
0
50
No
52
115
52
No
52
101
101
60
101
850/1150
101
101
0
101
10
101
10
101
1
101
102
102
102
35
102
35
103
0
103
10
103
10
103
1
103
259