PARAMETER GROUP
Options
EFB Protocol
NOTE(S):
a. 41 for Supply Fan Motor VFD, 42 for Exhaust Fan Motor VFD.
Table AC — VFD Parameters with CCN Points Configured with ComfortLink Controls
PARAMETER
PARAMETER
GROUP
TITLE
MOTOR NOM VOLT
MOTOR NOM CURR
Start-Up Data
MOTOR NOM FREQ
MOTOR NOM SPEED
MOTOR NOM POWER
Start/Stop/Dir
DIRECTION
ACCELER TIME 1
Accel/Decel
DECELER TIME 1
Motor Control
SWITCHING FREQ
Table AD — VFD Parameters Configured with ComfortLink Controls
PARAMETER GROUP
Start/Stop/Dir
Reference Select
Constant Speeds
System Controls
Start/Stop
Fault Functions
Automatic Reset
APPENDIX D — VFD INFORMATION (CONT)
Table AB — VFD Communication Parameters
PARAMETER TITLE
COMM PROT SEL
EFB PROTOCOL ID
EFB STATION ID
EFB BAUD RATE
EFB PARITY
EFB CTRL PROFILE
PARAMETER INDEX
(ACS320, ACH550 / 580)
9905 / 99.07
9906 / 99.06
9907 / 99.08
9908 / 99.09
9909 / 99.10
1003 / 20.21
2202 / 28.72
2203 / 28.73
2606 / 97.01
PARAMETER TITLE
PARAMETER INDEX
EXT1 COMMANDS
REF1 SELECT
CONST SPEED SEL
CONST SPEED 7
RUN ENABLE
FAULT RESET SEL
START ENABLE 1
START FUNCTION
STOP FUNCTION
COMM FAULT FUNC
COMM FAULT TIME
AR OVERCURRENT
AR OVERVOLTAGE
AR UNDERVOLTAGE
AR AI<MIN
AR EXTERNAL FAULT
PARAMETER INDEX
(ACS320, ACH550 / 580)
9802 / 58.01
5301 / 58.25
5302 / 58.03
5303 / 58.04
5304 / 58.05
5305 / 58.25
HVAC
CARRIER
DEFAULT
DEFAULT
230V,460V,575V
Refer to motor nameplate
1.0 In
Refer to motor nameplate
60 Hz
60 Hz
1750 rpm
1750 rpm
1.0 Pn
Refer to motor nameplate
FORWARD
REQUEST
30.0s
30.0s
30.0s
30.0s
4 kHz
8 kHz
HVAC DEFAULT
1001 / 20.01
DI1
1103 / 28.11
AI1
1201 / 28.22
DI3
1208 / 28.32
60 Hz
1601 / 20.40
NOT SEL
1604 / 31.11
KEYPAD
1608 / 20.41
DI4
2101 / 21.19
SCALAR FLYSTART
2102 / 21.03
COAST
3018 / 58.14
NOT SEL
3019 / 58.16
10.0 s
3104 / 31.12
Disable (0)
3105 / 31.12
Enable (1)
3106 / 31.12
Enable (1)
3107 / 31.12
Enable (1)
3108 / 31.12
Enable (1)
222
HVAC DEFAULT
CARRIER DEFAULT
NOT SEL (0)
LEN (6) / LEN (8)
0000 hex
0
9.6 kb/s
8 NONE 1
ABB DRV LIM
DCU PROFILE / ABB DRIVES
CCN POINT
SUPPLY FAN VFD
VFD1NVLT
VFD1NAMP
VFD1NFRQ
VFD1Nrpm
VFD1NPWR
VFD1MDIR
VFD1ACCL
VFD1DECL
VFD1SWFQ
CARRIER DEFAULT
COMM (10) / Embedded fieldbus
COMM (8) / FB A ref1
NOT SEL (0) / Always off
0 Hz
NOT SEL (0) / Not used
COMM (8) / EFB MCW bit 7
DI4 (4)
AUTO (1) / Automatic
RAMP (2)
CONST SP 7 (2) / Speed ref safe
10.0 s
Disable (0) / 0000 0000 0000 0000
Disable (0) / 0000 0000 0000 0000
Disable (0) / 0000 0000 0000 0000
Disable (0) / 0000 0000 0000 0000
Disable (0) / 0000 0000 0000 0000
0605 hex
41/42
a
38.4 kb/s
8 NONE 1
CCN POINT
EXHAUST FAN VFD
VFD2NVLT
VFD2NAMP
VFD2NFRQ
VFD2Nrpm
VFD2NPWR
VFD2MDIR
VFD2ACCL
VFD2DECL
VFD2SWFQ