APPENDIX B — CCN TABLES (CONT)
Table P — MAINTENANCE DISPLAY TABLES (cont)
DISPLAY NAME
ODF_VFD-A Actual Speed %
ODF_VFD-B Actual Speed %
Outdoor VFD A Ctrl Cmd%
Outdoor VFD B Ctrl Cmd%
Outdoor VFD A App Req%
Outdoor VFD B App Req%
Outdoor VFD A Ctrl Cmd%
Outdoor VFD B Ctrl Cmd%
Outdoor VFD SP Circuit A
Outdoor VFD SP Circuit B
Outdoor VFD A State
Outdoor VFD B State
Outdoor VFD A Fan CtrlMd
Outdoor VFD B Fan CtrlMd
SCTA SP At Low DP Ovrrd
SCTB SP At Low DP Ovrrd
SCTA SP At High DP Ovrrd
SCTB SP At High DP Ovrrd
Outdoor Air Enthalpy
Outside Air Temperature
Outside Air Rel.Humidity
Outside Air RH Sensor
OA Dewpoint Temp Limit
OutsideAir DewPoint Temp
OutsideAir Humidty Ratio
OA H2O Vapor Sat.Pressur
OA H2O Partial.Press.Vap
Space Enthalpy
Space Temperature
Controlling Space Temp
Space Relative Humidity
Space Temp Sensor
Space Air RH Sensor
Return Air Enthalpy
Return Air Temperature
Controlling Return Temp
Return Air Rel.Humidity
Return Air RH Sensor
Altitude........in feet:
Atmospheric Pressure
Space Relative Humidity
Return Air Rel.Humidity
Humidifier Relay
Humidifier Act.Curr.Pos.
Humidifier Command Pos.
Humidifier Setpoint
Humidifier Control Config
Humidifier Prop. Gain
Humidifier Integral Gain
Humidifier Deriv. Gain
Humidifier PID Run Rate
Space Air RH Sensor
Return RH Sensor
Supervisory Element #
Supervisory Bus
Supervisory Block Number
Average Occup. Heat Stp.
Average Occup. Cool Stp.
Average Unocc. Heat Stp.
Average Unocc. Cool Stp.
Average Zone Temperature
Average Occup. Zone Temp
Linkage System Occupied?
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Last Unoccupied Day
Last Unoccupied Time
RANGE
UNITS
0 to 100
%
0 to 100
%
%
%
%
%
%
%
degF
degF
degF
degF
degF
degF
dF
%
dF
dF
"Hg
"Hg
dF
dF
%
dF
dF
%
"Hg
%
%
%
%
%
sec
Enable/Disable
Enable/Disable
dF
dF
dF
dF
dF
dF
214
POINT NAME
WRITE STATUS
OVA_SPD
OVB_SPD
OV_A
OV_B
OV_A_ARQ
OV_B_ARQ
OV_A_TST
OV_B_TST
OV_A_SP
OV_B_SP
OV_A_ST
OV_B_ST
OV_A_CM
OV_B_CM
OV_ASCTL
OV_BSCTL
OV_ASCTH
OV_BSCTH
OAE
OAT
forcible
OARH
forcible
OARHSENS
config
OADEWCFG
forcible
OADEWTMP
OA_HUMR
OA_PWS
OA_PWS
SPE
SPT
forcible
SPACE_T
forcible
SPRH
forcible
SPTSENS
config
SPRHSENS
config
RAE
RAT
forcible
RETURN_T
forcible
RARH
forcible
RARHSENS
config
ALTITUDE
config
ATMOPRES
config
SPRH
forcible
RARH
forcible
HUMIDRLY
HUMDRPOS
HUMDCPOS
HUSP
config
HUMD_CFG
config
HUMID_PG
config
HUMID_IG
config
HUMID_DG
config
HUMDRATE
config
SPRHSENS
config
RARHSENS
config
SUPE-ADR
SUPE-BUS
BLOCKNUM
AOHS
AOCS
AUHS
AUCS
AZT
AOZT
LOCC
LNEXTOCD
LNEXTOCC
LNEXTUOD
LNEXTUNC
LLASTUOD
LLASTUNC